background image

  

ICC

 

ETH-1000 Quick Installation Guide

 

 

 

Page 2 

PN11145-1022

 

4.

 

Connect an Ethernet cable from an Ethernet switch to the ETH-1000 Ethernet port 

 

5.

 

Connect the RS-485 wiring (for serial communication) 

 

 
 
 

Note: 2-wire RS-485 requires a jumper between the A and Y 
terminals and a jumper between the B and Z terminals 

 

6.

 

Connect a power supply 

 

7VDC to 24VDC 

 Connect only DC voltage to the POWER and GND terminals. 

 

 

 

 

Power over Ethernet (PoE) 

 Ethernet port supports the IEEE 802.3af standard as a 

mode A or mode B powered device (PD). Requires a PoE power sourcing 
equipment such as a PoE endspan switch or midspan power injector. 

 

USB 

 Temporary connection to configure, troubleshoot, and optionally power the 

ETH-1000. USB cable may be connected while using any other power supply 
option, but should be removed under normal operation. 

 

7.

 

Installation is complete 

Terminal 

Network Connection 

A

 

RS-485 Receive Positive (Non-Inverting) 
RXD+ Data Signal 

RS-485 Receive Negative (Inverting) 
RXD- Data Signal 

RS-485 Transmit Positive (Non-Inverting) 
TXD+ Data Signal 

RS-485 Transmit Negative (Inverting) 
TXD- Data Signal 

GND 

RS-485 Common-Mode Reference 
0V Ground 

SHIELD / 

Chassis GND 

Cable Shielding Daisy-Chain Point 
This screw has no internal connection 

RS-485 terminals 

7VDC to 24VDC power terminals 