background image

ICC

 

INDUSTRIAL CONTROL COMMUNICATIONS, INC. 

Page 3 of 10 

05.23.2014 

 

 

0720-160-MC 

 

1600 Aspen Commons, Suite 210 
Middleton, WI, USA    53562 
Tel:  (608) 831-1255 
Fax:  (608) 831-2045 
Email: [email protected] 

Customizing the ETH

-

1000

’s Configuration

 

The ETH-1000 can be configured via USB using the ICC Configuration Studio. Certain network settings and 
BACnet settings may need to be modified to match a specific network configuration. To modify the gateway’s 
configuration, open the ICC Configuration Studio and connect the gateway via the included USB cable. The 
software will automatically recognize the connected device and upload the current configuration file stored on the 
gateway. The configuration must be downloaded back to the gateway after making any changes. The latest ICC 
Configuration Studio is available at 

http://www.iccdesigns.com/icc-configuration-studio.html

Ethernet Network Settings 

The network settings may need to be modified to be compatible with your network. These settings can be 
modified in the ICC Configuration Studio by selecting “Ethernet” in the Project Pane and changing the settings in 
the Settings Pane as shown in Figure 3. 
 

 

Figure 3:  Network Settings 

BACnet Communications Settings 

The UDP Port, Device Name, and Device Instance may need to be modified to be compatible with your network.  
These settings can be modified in the ICC Configuration Studio by selecting the corresponding items in the 
Project Pane and changing the settings in the Settings Pane. The UDP Port can be changed by selecting 
“BACnet/IP Server” and entering the desired UDP port number in the UDP Port field as shown in Figure 4. The 
Device Name and Instance can be changed by selecting “Device Object” and entering a value in the Device 
Name and Instance Number fields as shown in Figure 5. The default settings for the gateway are shown in 

Error! 

Not a valid bookmark self-reference.

 

 

Figure 4:  BACnet/IP UDP Port 

 

Содержание ETH-1000

Страница 1: ...to connect a preconfigured ETH 1000 gateway to a MSA Chillgard LC Refrigerant Monitor This document also contains the BACnet object mapping for the application and some troubleshooting tips For more i...

Страница 2: ...and G on the Chillgard LC to the gateway s terminal block at terminals TB 2 B TB 1 A and TB 6 GND as shown in Figure 2 This terminal block on the Chillgard LC will have wires for both the gateway and...

Страница 3: ...n studio html Ethernet Network Settings The network settings may need to be modified to be compatible with your network These settings can be modified in the ICC Configuration Studio by selecting Ethe...

Страница 4: ...160 MC 1600 Aspen Commons Suite 210 Middleton WI USA 53562 Tel 608 831 1255 Fax 608 831 2045 Email sales iccdesigns com Figure 5 BACnet Device Settings Table 1 Default BACnet Settings Setting Default...

Страница 5: ...definition AI2 S1 Concentration Gas Concentration for Sensor 1 PPM 96 1 000000 20 to 1050 AI3 S1 Alarm State Alarm State for Sensor 1 No Units 95 1 000000 0 None Bit 0 Caution Bit 1 Warning Bit 2 Ala...

Страница 6: ...ion AI22 S3 Concentration Gas Concentration for Sensor 3 PPM 96 1 000000 20 to 1050 AI23 S3 Alarm State Alarm State for Sensor 3 No Units 95 1 000000 0 None Bit 0 Caution Bit 1 Warning Bit 2 Alarm AI2...

Страница 7: ...1 S5 Gas Number Gas Number for Sensor 5 No Units 95 1 000000 0 to 44 Refer to manual for definition AI42 S5 Concentration Gas Concentration for Sensor 5 PPM 96 1 000000 20 to 1050 AI43 S5 Alarm State...

Страница 8: ...Bit 10 Flow Loss Bit 11 Under Voltage Bit 12 Temperature Bit 13 Prog Cksum Bit 14 Lamp Fail AI61 S7 Gas Number Gas Number for Sensor 7 No Units 95 1 000000 0 to 44 Refer to manual for definition AI62...

Страница 9: ...1 Alarm Sample 1 Alarm State On Off BI11 S2 Caution Sample 2 Caution State On Off BI12 S2 Warning Sample 2 Warning State On Off BI13 S2 Alarm Sample 2 Alarm State On Off BI21 S3 Caution Sample 3 Cauti...

Страница 10: ...hould light green when the gateway is powered and should flash green when the gateway is connected via USB i If this is not observed check the gateway s power b The RS 485 RX LED should flash red The...

Отзывы: