TECHNICAL SPECIFICATIONS
MATERIALS:
CASING:
Standard: Type 304 Stainless Steel
Optional: Galvalume, Type 430, 444 or 316 Stainless
FLUE:
Standard: Type 304 Stainless Steel
Optional: Type 444 or 316 Stainless Steel
INSULATION: "THERMOPLUS" HIGH TEMPERATURE MINERAL FIBRE
SIZE:
6" TO 24" Inside Diameter
ALLOWABLE FLUE GAS TEMPERATURES:
Maximum Continuous:
1000°F
Brief Forced Firing:
1400°F
Tested To: (3 X 10 min.)
2100°F
CLEARANCES:
To Combustible Materials:
2" Air Space Minimum
To Non-Combustible Materials:
No Clearance Required
NOTE:
NFPA 211 requires that all chimneys used on solid fuel
residential applications to be listed to UL 103HT
RIS Owner's Manual
ICC Chimney
3