3. Consider the locking mechanism before installation. To lock break out the “lock protector”
Place the detection part into the socket to be the mark on socket and on the detection part in line and than turn
the detection part clockwise cca 15
o
to fix.
Position of marks for insert of the detection part
Position of the marks after fix
into the socked
4. Repeat points 1 – 4 for all smoke detectors in the system.
5. Switch on the power supply of the the system.
6.
Press pushbutton ‘TEST MONTHLY’ of each installed smoke detector to TEST
Technical specification:
Type:
300-RE
Compliance:
EN 54 -7
Detection:
Optical chamber operating on the scattered light principle
Power supply:
External in the range from 12V DC to 24V DC
or
External 9V DC
Quiescent current:
<6mA (if terminal no 1 (+U) is used for power supply )
<12 uA – mean value - (if terminal no 2 (+9V) is used for power supply )
Alarm current:
<20 mA
Sounder:
85 dB(A) / 3m
Testing
Press push button (TEST MONTHLY)
Indication:
Normal condition
Blinking red LED every 50 s, contacts of the relay are in
the
rest
position
Low Voltage warning
Audible fault signal with red LED (every 40s)
ALARM
Audible alarm sounds and red LED blinks with per. (1s)
Relay is activated - contact NO is connected to COM
- contact NC is disconnected from COM
CHAMBER ERROR
Audible fault signal without red LED (every 40s)
Temperature:
-10
o
C to +55
o
C
Humidity: 95%
RH
Dimensions:
D=
118
mm,
H
=
42mm