3.  Consider the locking mechanism before installation. To lock break out the “lock protector” 
 

 
 
Place the detection part into the socket to be the  mark on socket and on the detection part in line and than turn 
the detection part clockwise cca 15

o

  to fix. 

 
Position of marks  for insert of the detection part  

 

     Position of the marks after fix   

into the socked 
 
 
4.  Repeat points 1 – 4 for all smoke detectors in the  system. 
5.  Switch on the power supply of the  the system. 

6. 

Press pushbutton ‘TEST MONTHLY’ of each installed smoke detector to TEST 

 

 
 

Technical specification:

  

 
Type: 

  300-RE 

Compliance: 

 

EN 54 -7  

Detection: 

 

Optical chamber operating on the scattered light principle 

Power supply: 

External in the range from 12V DC to 24V DC  

or 

External 9V DC   

  

Quiescent current: 

<6mA (if terminal no 1 (+U) is used for power supply ) 

  

 

 

<12 uA – mean value - (if terminal no 2 (+9V) is used for power supply ) 

Alarm current:   

<20 mA 

Sounder: 

 

85 dB(A) / 3m 

Testing   

 

Press push button (TEST MONTHLY)  

Indication: 

Normal condition  

Blinking red LED every 50 s, contacts of the relay are in  

 

   the 

rest 

position 

 

 

 

Low Voltage warning 

Audible fault signal with red LED (every 40s) 

 

 

 

ALARM 

 

Audible alarm sounds and red LED blinks with  per.  (1s) 

 

 

 

 

 

 

Relay is activated - contact NO is connected to COM 

 

 

 

 

 

 - contact NC is disconnected from COM 

CHAMBER ERROR 

Audible fault signal without red LED (every 40s) 

 

 

 

Temperature:  

-10

o

C  to  +55

o

Humidity:   95% 

RH 

Dimensions: 

 D= 

118 

mm, 

42mm 

   

 