QUICK GUIDE

FOR THE COMMISSIONING OF FIXED OR AUTOMATIC

POWER FACTOR CORRECTION EQUIPMENT

ALL65 rev7 jan18 cod.10098513

5 / 12

SAFETY NOTICE

Access to inner components for installation, setting, inspection and maintenance must be granted only to qualified personnel
in charge of such operations. Any activity must be carried out in compliance with the enforced regulations and legislation
concerning personal safety and using adequate protective tools. Unauthorized interventions might result in damaging or
compromising the power factor correction unit operation; in such case, the warranty clauses and the Manufacturer’s liability
would cease to be valid automatically.

The Manufacturer shall not be liable for direct or indirect damage caused to persons or objects in case of incorrect

installation or misuse of the unit.

CONNECTION TO THE MAINS

Connect the three mains phases to the terminals marked 1-2-3 or R-S-T (L1-L2-L3). Pay special attention to the
dimensioning of the power supply line to the power factor correction system and any operating and/or protective
devices, as they should be rated to withstand a current equal to 1.5 times the rated current of the capacitor bank.

CONNECTION OF THE EARTH WIRE

Connect the earth (ground) lead to the relative connection provided on the unit. The earth conductor size should
be equal at least to 60% of the phase conductor (e.g.: phase conductor, size 120mm

2

– earth conductor, size at

least 70mm

2

).

After the above described operations, proceed to switch on the unit. For non-automatic units, commissioning is
now terminated.
The operations in the following should only be carried out on automatic power correction units.

NOTE: all controller parameters are set at the factory except for the CT primary value. To change any

other values, please refer to the reactive power regulator manual attached to the equipment (also

available from the download site ww.icar.com) or contact ICAR PQS Service.

PRESETTING OF THE REACTIVE POWER REGULATOR

RPC 5LGA Regulator

At the start, the display will show a flashing “CT” notice.

Press the ▲ key and dial Current Transformer primary current. Once the setting is done, press the 

key to

confirm.

RPC 8LGA Regulator

At the start, the display will show a flashing “CT” notice.

Press the ▲ key and dial Current Transformer primary current. Once the setting is done, press the 

key to

confirm.

Содержание RPC 5LGA

Страница 1: ...a corrente nominale della batteria COLLEGAMENTO DEL CAVO DI TERRA Collegare il cavo di terra all apposita connessione predisposta sull apparecchiatura La dimensione del conduttore di terra dovrà essere almeno pari al 60 del conduttore di fase esempio cavo di fase da 120mm2 cavo di terra almeno 72mm2 Terminate le operazioni soprariportate dare tensione all apparecchiatura Nel caso di apparecchiatur...

Страница 2: ...o Confermare con il tasto b Inserire la lingua desiderata Il regolatore propone la schermata confermare con il tasto per passare alla schermata LINGUA In questa schermata selezionare la lingua con i tasti Confermare con il tasto c Inserire il valore del primario del TA esterno Il regolatore propone la schermata confermare con il tasto per passare alla schermata PRIMARIO TA In questa schermata sele...

Страница 3: ...ALE Con i tasti si accede alla visualizzazione degli altri step eventualmente presenti oltre quelli della schermata 1 4 Schermata menù principale Selezionare il menù desiderato con i tasti Confermare con Il menù selezionato si colora in negativo e compare al centro una sua descrizione testo Selezionare questa icona per impostare il funzionamento in manuale MAN Selezionare questa icona per impostar...

Страница 4: ... dei fusibili e dei contattori A22 Manutenzione straordinaria Eseguire le operazioni indicate in A20 e A21 e verificare condizioni condensatori o contattare il servizio di assistenza tecnica COLLEGAMENTO DEL TRASFORMATORE AMPEROMETRICO DI LINEA Il trasformatore amperometrico deve essere montato sulla fase non interessata dal prelievo del segnale voltmetrico da parte del regolatore di potenza reatt...

Страница 5: ...vices as they should be rated to withstand a current equal to 1 5 times the rated current of the capacitor bank CONNECTION OF THE EARTH WIRE Connect the earth ground lead to the relative connection provided on the unit The earth conductor size should be equal at least to 60 of the phase conductor e g phase conductor size 120mm2 earth conductor size at least 70mm2 After the above described operatio...

Страница 6: ...rom one number to the other Confirm with the key b Enter the desired language The power factor regulator shows the page confirm with the key to switch to the LANGUAGE page In this page select the language with the keys and confirm with the key c Enter the external CT primary value The power factor regulator shows the page confirm with the key to switch to the CT PRIMARY page In this page select th...

Страница 7: ...ible to move through the available pages With the key the MAIN MENU page is accessed With the keys to the display of additional steps that may be present in addition to those of the page 1 4 is accessed Main menu Select the desired menu with the keys and confirm with the key The selected menu is highlighted in reverse and at the centre a text description appears Select this icon to set the MANUAL ...

Страница 8: ...ach step current fuses and contactors A22 Extraordinary maintenance Perform the operations in A20 and A21 and check the capacitors conditions or contact technical service CONNECTION OF THE LINE CURRENT TRANSFORMER Mount the current transformer on the phase not concerned with the pick up of the voltage signal by the reactive power regulator usually phase L1 also marked by R and before the branch su...

Страница 9: ...e fil de terre à la borne correspondante de l équipement Le dimensionnement du fil de terre devra être au minimum égal à 60 de la section des fils de phase pour example pour une section de fil de phase de 120mm2 la section du fil de terre devra être au minimum de 70mm2 Après réalisation des opérations décrite ci dessus vous pourrez procéder à la connexion de la batterie Cette dernière opération cl...

Страница 10: ...touche b Sélectionnez le langage désiré Le contrôleur d énergie réactive indique la page Confirmez avec la touche pour atteindre la page de sélection LANGUE Sur cette page selectionnez le langage à l aide des touches Confirmez avec la touche c Entrez la valeur du courant primaire du TI Le contrôleur d énergie réactive indique la page Confirmez avec la touche pour atteindre la page de sélection PRI...

Страница 11: ... courant de l installation en temps réel A l aide des touches il est possible de balayer les différentes pages disponibles Avec la touche on peut accéder au menu principal Avec les touches il est possible d accéder à d éventuels autres gradins disponibles en addition de ceux figurant en page 1 4 Menu principal Sélectionnez le menu désiré avec les touches Confirmez avec la touche Le menu sélectionn...

Страница 12: ... Nettoyer le filtre interne du système de ventilation A21 Maintenance de routine Vérifier les courants de chaque gradin l état des fusibles et des contacteurs A22 Maintenance exceptionnelle Réaliser les opérations en A20 et en A21 et vérifier les contactes des supports techniques des condensateurs CONNECTION SUR LE RESEAU DU TRANSFORMATEUR DE COURANT TC Montez le transformateur de courant sur la p...

Отзывы: