Installing the 2U chassis fan assembly
To install the 2U chassis fan assembly, complete the following steps.
Fan assembly
1. Touch the static-protective package that contains the fan assembly to any
unpainted
metal surface on the outside of the chassis; then, remove the fan
assembly from the package.
2. Orient the fan assembly over the opening in the chassis. Make sure that the
power connector on the fan assembly aligns with the connector on the power
supply.
3. Lower the fan assembly into the chassis and press down on the tab above the
power connector to make sure that it is fully seated.
4. Install the top cover (see “Installing the 2U chassis top cover” on page 83).
5. Install the chassis in the iDataPlex rack (see “Installing the 2U chassis in a Type
7825 iDataPlex rack” on page 124).
6. Install any system-board trays that you removed (see “Installing the
system-board tray in a 2U chassis” on page 76).
Chapter 4. Removing and replacing server components
81