2.
Place the fan module into the rear chassis cavity so that it rests on the chassis.
Gently push the fan module into the chassis and the guide pin will self-align to
the top and bottom chassis matching slots. After fully engaged, tighten the
captive screws to 5 in-lb to secure fan module to chassis. The fan module will
just snap in.
3.
If the switch is powered on, listen for the fans; you should immediately hear
them operating. If you do not hear them, ensure that the fan module is inserted
completely in the chassis and the outside surface of the fan module is flush
with the outside surface of the chassis.
4.
Verify that the Fan Status LED is green. If the LED is not green, one or more
fans are faulty. If this occurs, contact your customer service representative for a
replacement part.
Removing a Fan Module
About this task
Note:
When removing the fan module, keep your hands and fingers away from
the spinning fan blades. Let the fan blades completely stop before you remove the
fan module.
To remove the fan module from the IBM c-type SAN Device, follow these steps:
Procedure
1.
Loosen the four captive screws on the module being removed.
2.
Grasp the handles of the fan module with both hands and pull it outward to
unseat the power connector from the backplane.
3.
Pull the fan module fully out of the chassis.
Starting Up the Switch
This section provides the following information:
v
“Verifying Component Installation”
v
“Powering Up the Switch” on page 88
Note:
Hazardous voltage or energy is present on the backplane when the system is
operating. Use caution when servicing.
CAUTION:
During this procedure, wear grounding wrist straps to avoid ESD damage to the
switch.
Note:
The 3000-W power supplies provide power according to the input voltage. If
they are in redundant rather than combined mode at 110 VAC, they may be unable
to provide adequate power to all modules present in the system. See Appendix A,
“Product Specifications,” on page 99.
Verifying Component Installation
About this task
Note:
Blank faceplates and cover panels serve three important functions: they
prevent exposure to hazardous voltages and currents inside the chassis; they
contain electromagnetic interference (EMI) that might disrupt other equipment; and
they direct the flow of cooling air through the chassis. Do not operate the system
unless all cards, faceplates, front covers, and rear covers are in place.
Chapter 3. Installing the IBM c-type SAN Device
87
Содержание SAN192C-6
Страница 2: ......
Страница 8: ...vi SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 10: ...viii SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 24: ...xxii SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 114: ...90 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 122: ...98 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 142: ...Figure 44 AJK5 Figure 45 AJJX Figure 46 AJK4 118 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 143: ...Figure 47 AJK2 Figure 48 AJK1 Figure 49 AJJY Appendix B Cable and Port Specifications 119 ...
Страница 144: ...Figure 50 AJJV 120 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 146: ...122 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 158: ...134 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Страница 159: ......
Страница 160: ...IBM Part Number 02JD693 Printed in USA SC27 9276 00 1P P N 02JD693 ...