Determining and marking the location in the rack
You might need to determine where to install the system unit into the rack.
Procedure
1.
Read the Rack safety notices (http://www.ibm.com/support/knowledgecenter/POWER8/p8hbf/
racksafety.htm).
2.
Determine where to place the system unit in the rack. As you plan for installing the system unit in a
rack, consider the following information:
v
Organize larger and heavier units into the lower part of the rack.
v
Plan to install units into the lower part of the rack first.
v
Record the Electronic Industries Alliance (EIA) locations in your plan.
Note:
The server is two EIA units high. An EIA unit is 44.55 mm (1.75 in.) in height. The rack
contains three mounting holes for each EIA unit of height. This system unit, therefore, is 89 mm (3.5
in.) high and covers six mounting holes in the rack.
3.
If necessary, remove the filler panels to allow access to the inside of the rack enclosure where you
plan to place the unit, as shown in Figure 1 on page 3.
2
Installing the System and Ordered Parts for the 8335-GCA or 8335-GTA
Содержание S822LC
Страница 2: ......
Страница 16: ...xiv Installing the System and Ordered Parts for the 8335 GCA or 8335 GTA...
Страница 104: ...88 Installing the System and Ordered Parts for the 8335 GCA or 8335 GTA...
Страница 122: ...106 Installing the System and Ordered Parts for the 8335 GCA or 8335 GTA...
Страница 125: ...Figure 78 Connecting the power cord to the power supply Power supplies 109...
Страница 126: ...110 Installing the System and Ordered Parts for the 8335 GCA or 8335 GTA...
Страница 138: ...122 Installing the System and Ordered Parts for the 8335 GCA or 8335 GTA...
Страница 139: ......
Страница 140: ...IBM Printed in USA...