Use the following table to map the slot number information in the operating system log to the PCIe
adapter description and service action.
Table 8. Slot numbers, adapter descriptions, and service action for the 8335-GCA or 8335-GTA.
Slot information from the log
PCIe adapter description
Service action
Slot1
PCIe adapter 1
Replace the PCIe adapter indicated in
the PCIe adapter description column.
Go to “8335-GCA and 8335-GTA
locations” on page 111 to identify the
physical location and the removal
and replacement procedure.
Slot2
PCIe adapter 2
Slot3
PCIe adapter 3
Slot4
PCIe adapter 4
Slot5
PCIe adapter 5
Table 9. Slot numbers, adapter descriptions, and service action for the 8335-GTB
Slot information from the log
PCIe adapter description
Service action
Slot1
PCIe adapter 1
Replace the PCIe adapter indicated in
the PCIe adapter description column.
Go to “8335-GTB locations” on page
121 to identify the physical location
and the removal and replacement
procedure.
Slot2
PCIe adapter 2
Slot3
PCIe adapter 3
Table 10. Slot numbers, adapter descriptions, and service action for the 8348-21C.
Slot information from the log
PCIe adapter description
Service action
Slot1
PCIe adapter 1
Replace the PCIe adapter indicated in
the PCIe adapter description column.
Go to “8348-21C locations” on page
133 to identify the physical location
and the removal and replacement
procedure.
Slot2
PCIe adapter 2
Slot3
PCIe adapter 3
Slot4
PCIe adapter 4
Identifying the location of the GPU
The error message provides information to help you to determine the location of the graphics processing
unit (GPU).
On an 8335-GCA or 8335-GTA system, the log might contain an error message similar to the following
text:
EEH: PHB#0 failure detected, location: Slot5
On an 8335-GTB system, the log might contain an error message similar to the following text:
EEH: PHB#0 failure detected, location: GPU1
If you have an 8335-GTB system with Red Hat Enterprise Linux 7.4 or later, and if you get an error
message with only PCI bus information (for example,
0002:01:00.0
), you can determine the GPU slot
information by using the
lshw
command. Complete the following steps:
1.
Record the PCI bus information that is in the error message.
2.
Log in to the operating system with root authority.
3.
Type the following command and press Enter:
lshw -class display
4.
Determine the GPU slot that is associated with the PCI bus information that you recorded in step 1.
22
Problem analysis, system parts, and locations for the 8335-GCA, 8335-GTA, 8335-GTB, and 8348-21C
Содержание Power System 8335-GCA
Страница 2: ......
Страница 16: ...xiv Problem analysis system parts and locations for the 8335 GCA 8335 GTA 8335 GTB and 8348 21C ...
Страница 133: ...System parts Figure 6 System parts Finding parts and locations 117 ...
Страница 160: ...144 Problem analysis system parts and locations for the 8335 GCA 8335 GTA 8335 GTB and 8348 21C ...
Страница 172: ...156 Problem analysis system parts and locations for the 8335 GCA 8335 GTA 8335 GTB and 8348 21C ...
Страница 173: ......
Страница 174: ...IBM ...