Figure 6. Sample illustration to show space around the rack
For a Model 092 expansion enclosure, use the recommended measurements that are given in Table 11 on
Table 11. Service clearance requirements
Front
1
Back
1200 mm (47 in.)
1000 mm (39 in.)
1
Storage racks require larger service clearances in the front of the rack.
For more information on the layout of the room, see Computer room layout
See Site preparation and physical planning section to help you prepare your physical site for the
installation of a Model 092 expansion enclosure.
Additional space requirements
Ensure that these additional space requirements, as shown in Table 12 on page 30, are available around
the enclosures.
Table 12. Clearances
Location
Additional space requirements
Reason
Left and right sides
50 mm (2 in.)
Cooling air flow
Back
Minimum: 100 mm (4 in.)
Cable exit
30 IBM Elastic Storage System 5000: Model 092 Hardware Guide
Содержание Elastic Storage System 5000 Series
Страница 1: ...IBM Elastic Storage System 5000 Version 6 0 1 Model 092 Hardware Guide IBM SC28 3135 00...
Страница 8: ...viii...
Страница 10: ...24 Enclosure models and rack requirements 74 x...
Страница 14: ...xiv IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 32: ...18 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 36: ...22 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 51: ...Figure 11 Cable connectivity from I O servers Chapter 4 Planning for hardware 37...
Страница 86: ...72 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 90: ...76 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 98: ...84 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 100: ...86 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 101: ......
Страница 102: ...IBM Product Number 5765 DME 5765 DAE SC28 3135 00...