Table 77. Single-phase input voltages and frequencies (continued)
Characteristic
Voltage (single-phase)
Steady-state input frequencies
50 ± 3 or 60 ± 3.0 Hz
PLD input frequencies (<10 seconds)
50 ± 3 or 60 ± 3.0 Hz
1.
Regions such as the United States and Canada require 20% derating for power
distribution circuits. For these regions, a minimum 50 A circuit breaker is required for a
40 Amp rated system such as the DS8886. Verification of applicable local standards is
required for system installation. Some configuration restrictions to limit power
consumption can allow reduced breaker ratings on a regional basis.
Table 78. Three-phase input voltages and frequencies
Characteristic
Three-phase delta (3Ø
∆
)
Three-phase wye (3ØY:
LL[Line-to-Line])
Nominal input voltages
200, 208, 220, or 240 RMS V
AC
380, 400, or 415 RMS V AC
Minimum tolerated
input voltage
180 RMS V AC
315 RMS V AC
Maximum tolerated
input voltage
256 RMS V AC
456 RMS V AC
System maximum
current rating
30 Amps for Japan
24 Amps for other regions
17 Amps
Wall breaker rating (3
ph)
1
30 - 60 Amps
20 - 32 Amps
Steady-state input
frequencies
50 ± 3 or 60 ± 3.0 Hz
50 ± 3 or 60 ± 3.0 Hz
PLD input frequencies
(<10 seconds)
50 ± 3 or 60 ± 3.0 Hz
50 ± 3 or 60 ± 3.0 Hz
1.
Regions such as the United States and Canada require 20% derating for power
distribution circuits. For these regions, a minimum 50 A circuit breaker is required for a
40 Amp rated system such as the DS8886. Verification of applicable local standards is
required for system installation. Some configuration restrictions to limit power
consumption can allow reduced breaker ratings on a regional basis.
Power connector requirements
Ensure that the site where you plan to install the storage system meets the power
connector requirements.
Table 79 on page 159 shows the power cords and the inline connectors and
receptacle types that they support. Find the power cord row that is appropriate for
your site. Ensure that your site meets the specified power connector requirements.
158
DS8880 Introduction and Planning Guide
Содержание DS8880 Series
Страница 1: ...IBM DS8880 Version 8 Release 5 Introduction and Planning Guide GC27 8525 16 IBM...
Страница 12: ...xii DS8880 Introduction and Planning Guide...
Страница 52: ...40 DS8880 Introduction and Planning Guide...
Страница 68: ...56 DS8880 Introduction and Planning Guide...
Страница 138: ...126 DS8880 Introduction and Planning Guide...
Страница 184: ...172 DS8880 Introduction and Planning Guide...
Страница 190: ...178 DS8880 Introduction and Planning Guide...
Страница 194: ...182 DS8880 Introduction and Planning Guide...
Страница 200: ...188 DS8880 Introduction and Planning Guide...
Страница 206: ...194 DS8880 Introduction and Planning Guide...
Страница 208: ...196 DS8880 Introduction and Planning Guide...
Страница 216: ...204 DS8880 Introduction and Planning Guide...
Страница 220: ...208 DS8880 Introduction and Planning Guide...
Страница 222: ...210 DS8880 Introduction and Planning Guide...
Страница 243: ......
Страница 244: ...IBM Printed in USA GC27 8525 16...