![IBM 9910-E36 Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/ibm/9910-e36/9910-e36_service-manual_3383086004.webp)
IBM Asia Pacific Hardware Announcement AG11-0027
IBM is a registered trademark of International Business Machines Corporation
4
To assure installability and serviceability in non-IBM industry-standard racks,
review the installation planning information for any product-specific installation
requirements.
Operating environment
Model E36
• Temperature: 0 to 40 degrees C (32 to 104 degrees F)
• Relative humidity: 0% to 95% noncondensing
• Audible noise at one meter: <55 dBA
• Operation elevation: 0 - +3000 m (0 - 10,000 ft)
• Input voltage: E36 - 230V (voltage range - 160-286 V ac)
• Output voltage: E35 - 208V
Software requirements
If the relay-serial card (feature number 2944) is used, no software is required. IBM
has a platform managed solution that allows the relay card signals from the UPS
to be broadcast to IBM i, AIX, and Linux partitions. Each partition has a default
shutdown time.
IBM UPS Manager software can be used with the network management card (feature
number 2945) or the UPS RS232 serial port. AIX 6 and AIX 7 are supported as well
as several versions of Red Hat Enterprise Linux 4 and Red Hat Enterprise Linux 5.
For a listing of current supported operating systems and information about
Powerware power system, network, and enterprisewide monitoring and control
software, refer to the following website
http://www.powerware.com/software/products.asp
Planning information
Customer responsibilities
The 9910 Model E36 is designated as customer setup.
If the model is not ordered with the iSeries and pSeries rack, the client will be
responsible for the installation of external cables, the power system module, and
the battery module. Clients who request IBM service personnel to perform these
activities are subject to a charge. Client responsibilities include:
• Adequate site and system planning, and preparation
• Receipt, unpacking, and placement of the system unit
• Ordering, installing, and maintaining cables with associated parts for attaching to
the pSeries model
• Using and following the problem determination procedures in the operators guide
• Installing power system management software and setting power system run-
time parameters
• Installing feature number 2945 and 2944 interface cards
Cable orders
9910 Model E35/E36
Power (electrical) cables
The input (mains) power connection to the 9910-E35/E36 is an IEC C20 16 amp
connector. The input (mains) power cord from the power system to the utility
(mains) is determined based upon the country or locality. Refer to the following
9910-E35/E36 input power cord table: