1.
Align the fan with its slot in the system
unit.
2.
Gently push the fan into the system unit.
3.
Press on the fan to ensure that it is
completely seated. The fan starts to run
when it is correctly installed.
4.
Move the slider bar to the right and
tighten the screws.
6.
Go to “MAP 2410: 7031-D24 or 7031-T24 repair verification” on page 42 to verify the repair. For a
server level repair verification, go to your host server's service guide.
This completes this procedure.
Power supply
Use this procedure to service the power supply.
1.
You may service the power supply concurrently or non-concurrently. To service the power supply concurrently, begin
with Step 2. Otherwise, begin with Step 3.
2.
The component will be serviced concurrently. Power should not be removed from the unit containing the FRU in the
location field above during this procedure. Go to step 4.
3.
The failing component will not be replaced concurrently. Power should be removed from the enclosure containing the
FRU in the location field above. If this enclosure is powered on, power it off now. Do not apply power to the
enclosure until directed to do so in this procedure.
4.
5786, 5787, 7031-D24, and 7031-T24 removal and replacement procedures
21
Содержание 5786
Страница 1: ...Power Systems 5786 5787 and 7031 models D24 and T24 removal and replacement procedures ...
Страница 2: ......
Страница 3: ...Power Systems 5786 5787 and 7031 models D24 and T24 removal and replacement procedures ...
Страница 6: ...iv Removal and replacement procedures ...
Страница 38: ...26 Removal and replacement procedures ...
Страница 44: ...32 Removal and replacement procedures ...
Страница 62: ...50 Removal and replacement procedures ...
Страница 63: ......
Страница 64: ... Printed in USA ...