3. Click
OK
. The computer creates a communication connection.
4. Click
Call
, and then click
Disconnect
.
5. Click
File -> Properties
. Set the computer ASCII settings as shown in the
following illustration.
6. Type
GH
and press Enter.
The UPS replies with a list of events that includes the event type, ID, date and
time, and name. For example:
Alarm
#199
03/10/2010 10:55:38
Battery Disconnected
Notice #025
03/09/2010 08:30:40
Output Overload
Event
#181
03/09/2010 07:29:39
UPS Control Power ON
7. Right-click the text that you want, and click
Copy
. The list of events is copied to
your computer clipboard.
8. Press Ctrl+V to paste the text into an email or document.
Chapter 6. Troubleshooting
57
Содержание 11000 VA LCD 5U
Страница 1: ...11000 VA LCD 5U Rack UPS 11000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...
Страница 2: ......
Страница 3: ...11000 VA LCD 5U Rack UPS 11000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...
Страница 13: ...Taiwan Class A compliance statement 71 Index 73 Contents xi...
Страница 14: ...xii 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 40: ...26 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 56: ...42 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 60: ...46 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 76: ...62 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 86: ...72 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 90: ...76 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 91: ......
Страница 92: ...Part Number 60Y1454 Printed in USA 1P P N 60Y1454...