7. Connect the input and ground wires to the terminal block according to the
following illustration and Table 4.
1 2 3
Terminal position
Table 4. UPS wiring specifications
Wire functions
Terminal
position
UPS wire
function
Terminal wire
size rating
1
Tightening
torque
Input
1
Input ground
16 - 35 mm
2
(8 - 2 AWG)
1.69 Nm (15
inch-pounds)
2
L2 / Neutral In
3
L1 In
1
Use the following minimum wire size:
v
8 AWG for equipment grounding wire, 75°C copper wire minimum
v
4 AWG for input line and neutral wires, 75°C copper wire minimum
8. Replace the terminal block cover.
9. Continue to “UPS initial startup” on page 25.
18
11000 VA UPS and 11000 VA EBM: Installation and Maintenance Guide
Содержание 11000 VA LCD 5U
Страница 1: ...11000 VA LCD 5U Rack UPS 11000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...
Страница 2: ......
Страница 3: ...11000 VA LCD 5U Rack UPS 11000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...
Страница 13: ...Taiwan Class A compliance statement 71 Index 73 Contents xi...
Страница 14: ...xii 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 40: ...26 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 56: ...42 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 60: ...46 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 76: ...62 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 86: ...72 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 90: ...76 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Страница 91: ......
Страница 92: ...Part Number 60Y1454 Printed in USA 1P P N 60Y1454...