Hard-wiring the UPS input (for licensed electrician only)

CAUTION:
The product might be equipped with a hard-wired power cable. Ensure that a
licensed electrician performs the installation per the national electrical code.
(C022)

The 11000 VA UPS model requires a dedicated branch circuit that meets the
following requirements:

v

A breaker that is wall-mounted and readily accessible to the operator:

A 63 A (for Europe) or 80 A (for North America) 2-pole circuit breaker to provide
short circuit and overcurrent protection.

(For Europe) The breaker meets the IEC/EN 60934 standard and has a contact
air gap of at least 3 mm.

v

A two-pole disconnection device between the UPS output and the load (see the
circuit breaker diagram).

v

200 - 240 V ac, 50/60 Hz.

v

Flexible metal conduit (for ease of service and maintenance).

The following illustration shows the circuit breaker diagram.

To hard-wire the UPS input, complete the following steps:

1. Turn off the utility power at the distribution point where you will connect the

UPS. Be absolutely sure that there is no power.

16

11000 VA UPS and 11000 VA EBM: Installation and Maintenance Guide

Содержание 11000 VA LCD 5U

Страница 1: ...11000 VA LCD 5U Rack UPS 11000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...

Страница 2: ......

Страница 3: ...11000 VA LCD 5U Rack UPS 11000 VA UPS 3U Extended Battery Module Installation and Maintenance Guide...

Страница 4: ...Safety Notices and Environmental Notices and User Guide documents on the IBM Documentation CD and the Warranty Information document that comes with the product Second Edition June 2011 Copyright IBM C...

Страница 5: ...lleert eerst de veiligheidsvoorschriften Ennen kuin asennat t m n tuotteen lue turvaohjeet kohdasta Safety Information Avant d installer ce produit lisez les consignes de s curit Vor der Installation...

Страница 6: ...tement are in the Systems Safety Notices document under D005a Be sure to read all caution and danger statements in this document before you perform the procedures Read any additional safety informatio...

Страница 7: ...v Connect any equipment that will be attached to this product to properly wired outlets v When possible use one hand only to connect or disconnect signal cables v Never turn on any equipment when ther...

Страница 8: ...ss for the collection of this battery For information call 1 800 426 4333 Have the IBM part number for the battery unit available when you call C004 CAUTION or 32 kg 70 5 lb or 32 55 kg 70 5 121 2 lb...

Страница 9: ...es are not to be used as shelves or work spaces Do not place objects on top of rack mounted devices v Each rack cabinet might have more than one power cord Be sure to disconnect all power cords in the...

Страница 10: ...pull out more than one drawer at a time The rack might become unstable if you pull out more than one drawer at a time v For fixed drawers This drawer is a fixed drawer and must not be moved for servi...

Страница 11: ...Connecting the UPS internal batteries 19 Disconnecting the UPS internal batteries 22 UPS initial startup 25 Chapter 3 Operating the uninterruptible power supply 27 Control panel 27 Operating modes 28...

Страница 12: ...encing the alarm 61 Appendix A Getting help and technical assistance 63 Before you call 63 Using the documentation 63 Getting help and information from the World Wide Web 63 Software service and suppo...

Страница 13: ...Taiwan Class A compliance statement 71 Index 73 Contents xi...

Страница 14: ...xii 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...

Страница 15: ...6 This document contains the following information v Setting up the UPS v Connecting an extended battery module to the UPS v Starting and configuring the UPS v Solving problems If firmware and documen...

Страница 16: ...abled insert the CD into the CD drive The Documentation Browser starts automatically v If Autostart is disabled or is not enabled for all users use one of the following procedures If you are using a W...

Страница 17: ...ck a document to view it and press Ctrl F to use the Acrobat search function or press Alt F to use the xpdf search function within the document Click Help for detailed information about using the Docu...

Страница 18: ...uto sensing at first power up Maximum RMS current in normal mode battery fully charged 59 3 amps 200 V 59 0 amps 208 V 58 4 amps 230 V Input voltage range for main operations V ac 184 to 276 V ac Nomi...

Страница 19: ...module specifications Specification 11000 VA UPS 3U extended battery module Height 127 mm 5 in Width 483 mm 19 in Depth 740 mm 29 1 in Weight 79 kg 174 lb Voltage 288 V 24 x 12 V 9 Ah Internal circuit...

Страница 20: ...enient or problem situations v Attention These notices indicate potential damage to programs devices or data An attention notice is placed just before the instruction or situation in which damage coul...

Страница 21: ...ols to install the UPS v One number 2 Phillips screwdriver for use with the rack mount kit and terminal block cover v One flat blade screwdriver for wiring the terminal block Inventory checklist The U...

Страница 22: ...ation shows the front view of the UPS OK 10 0 6 m in 1500VA 208V 60h z UPS ON For more information about the control panel on the front of the UPS see Control panel on page 27 8 11000 VA UPS and 11000...

Страница 23: ...rols and connectors on the rear of the 11000 VA LCD 5U rack UPS 200 V 208 V 230 V Front view of the extended battery module The following illustration shows the front view of the 3U extended battery m...

Страница 24: ...iew of the 11000 VA 3U extended battery module Rack installation To install the UPS or extended battery module in a rack cabinet see the IBM Rack Installation Instructions document that comes with the...

Страница 25: ...y module cable into the UPS battery connector quickly and firmly Note You can connect only one extended battery module to the UPS To connect an extended battery module to the UPS complete the followin...

Страница 26: ...e extended battery module connector cover must be installed as a safety precaution Extended battery module connector cover Uninterruptible power supply Extended battery module 3 Align the extended bat...

Страница 27: ...of the UPS complete the following steps 1 If you are installing the IBM UPS Manager software connect a computer to the UPS by using one of the communication cables that come with the UPS For more info...

Страница 28: ...ry power are also shut down immediately When the remote emergency power off switch is reset the connected devices do not return to battery power until the UPS is restarted manually Notes 1 The remote...

Страница 29: ...the UPS Note The orientation of the remote emergency power off port on your UPS model might be different from what is shown in the following illustration You might have to rotate the remote emergency...

Страница 30: ...aker to provide short circuit and overcurrent protection For Europe The breaker meets the IEC EN 60934 standard and has a contact air gap of at least 3 mm v A two pole disconnection device between the...

Страница 31: ...ring access entry and attach the conduit fitting to the panel Strip 1 5 cm 0 5 in of insulation from the end of each incoming wire 6 CAUTION The UPS does not have an automatic protection device agains...

Страница 32: ...e size rating1 Tightening torque Input 1 Input ground 16 35 mm2 8 2 AWG 1 69 Nm 15 inch pounds 2 L2 Neutral In 3 L1 In 1 Use the following minimum wire size v 8 AWG for equipment grounding wire 75 C c...

Страница 33: ...nt bezel Press the two side latches toward each other to release the bezel and pull the bezel away OK OK 100 6 min 2 Loosen the thumbscrew on the left battery retention bracket 1 slide the bracket to...

Страница 34: ...3 and then remove it OK OK 100 6 min R 4 Connect the three internal battery connectors OK OK 100 6 min Note A small amount of arcing might occur when you connect the batteries This is normal and does...

Страница 35: ...ll the left battery retention bracket a Slide the left battery retention bracket to the right and into the slot 1 OK OK 100 6 min L b Rotate the battery retention bracket toward the UPS 2 Make sure th...

Страница 36: ...bezel Press the two side latches toward each other to release the bezel and pull the bezel away OK OK 100 6 min 2 Loosen the thumbscrew on the left battery retention bracket 1 slide the bracket to th...

Страница 37: ...ery retention bracket 1 slide the bracket to the left 2 rotate the bracket out 3 and then remove it OK OK 100 6 min R 4 Disconnect all three internal battery connectors OK OK 100 6 min Chapter 2 Insta...

Страница 38: ...left battery retention bracket a Slide the left battery retention bracket to the right and into the slot 1 OK OK 100 6 min L b Rotate the battery retention bracket toward the UPS 2 Make sure that the...

Страница 39: ...nd to change other factory set defaults see Chapter 3 Operating the uninterruptible power supply on page 27 9 If you installed an optional remote emergency power off switch make sure that the function...

Страница 40: ...26 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...

Страница 41: ...rol panel Escape button On Off button Down button OK button The UPS has a graphical liquid crystal display LCD with dual color backlight Standard backlight is used to light the display with white text...

Страница 42: ...PS has the following operating modes v Normal v High Efficiency v Converter v Battery v Bypass v Standby Note If the UPS is unable to continue operating normally it might attempt to save data and foll...

Страница 43: ...in Standby mode The UPS is not supporting the load but is ready to assume the load on command Turning on the UPS After the UPS is connected to the power source it enters Standby mode To turn on the U...

Страница 44: ...Troubleshooting on page 55 The following table describes the available battery status messages Only one battery status is available at a time Table 6 Battery status messages Battery status Descriptio...

Страница 45: ...Normal Mode Command Sent message for 5 seconds The option then changes to Go to Bypass Battery test Schedule Battery Test yes Cancel Battery test no Starts a manual battery test See Testing a battery...

Страница 46: ...inese Russian Korean Traditional Chinese English User password Enabled Disabled If the user password is enabled the default password is USER Note If you enter an incorrect password the message Wrong P...

Страница 47: ...isabled Overload alarm level 10 20 30 100 If 100 the UPS issues an Output Overload alarm at load 100 Note Output Overload Level 1 by default is set to 100 and is configurable from 10 to 100 in 10 incr...

Страница 48: ...ended battery module on page 40 0 Battery low alarm Immediate 2 min 3 min 5 min If you select a value the battery low alarm is triggered when the set amount of backup time approximately remains in the...

Страница 49: ...s the OK button 2 Press the down button to scroll to Go to Bypass and press the OK button The text on the screen changes to Manual Bypass Command Sent Transferring from Bypass to Normal Mode To transf...

Страница 50: ...utput frequency setting Input frequency Hz Output frequency Hz UPS behavior 50 50 Hz 47 53 47 53 UPS in Converter mode synchronizes the output frequency with the input frequency 45 46 or 54 65 50 UPS...

Страница 51: ...notices and alarms 3 Press the escape X button to return to the previous menu Behavior on overload The following table explains how the UPS responds to an overload condition Table 10 Behavior on over...

Страница 52: ...the following illustration The shading does not appear on the chassis Controlling load segments through the display To control the load segments through the display complete the following steps 1 Fro...

Страница 53: ...onfirm 6 Repeat step 3 to step 5 to set the other load segment if applicable Notes 1 Load segment on off commands that are issued through the Control menu override the user settings for load segments...

Страница 54: ...own warning prematurely Conversely if the UPS is configured for the extended battery module but the extended battery module is not connected to the UPS the UPS reports more battery time remaining and...

Страница 55: ...or High Efficiency mode with no active alarms v The load is greater than 10 v The bypass voltage is usable Configuring automatic battery tests To configure the automatic battery tests complete the fol...

Страница 56: ...42 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...

Страница 57: ...t the IBM UPS Manager CD that comes with the UPS into the CD or DVD drive If the Software Wizard install menu does not automatically open see the CD_ReadMe txt file and follow the steps to manually op...

Страница 58: ...nctions are described in Table 11 RS 232 connector 5 4 3 2 1 9 8 7 6 Table 11 RS 232 connector pin assignments Pin Signal name Function Direction from the UPS 1 Unused Not applicable 2 Tx Transmit to...

Страница 59: ...ng configuring and using the network management card see the IBM Network Management Card User s Guide on the IBM Documentation CD that comes with the UPS For details about disabling control commands f...

Страница 60: ...46 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...

Страница 61: ...12 11000 VA UPS CRU listing Description MTM or part number CRU part number Tier 1 UPS chassis 11000 VA 208 V 230 V 5395 9KX 81Y2321 Battery module This CRU part contains the two battery modules that...

Страница 62: ...ed precautions Keep unauthorized personnel away from batteries Batteries can present a risk of electrical shock or burn from high short circuit current Determine whether the battery is inadvertently g...

Страница 63: ...n disconnect the UPS 2 Wait 60 seconds while the internal processor shuts down before you disconnect the battery To replace the battery modules complete the following steps 1 Remove the UPS lower fron...

Страница 64: ...of the way OK OK 100 6 min 5 Remove the left internal battery module Important Each internal battery module weighs 32 kg 71 lb and requires three people to safely to lift it With the required three pe...

Страница 65: ...gulations OK OK 100 6 min 7 With the required three people carefully slide one new battery module into the UPS Repeat this step for the second battery module 8 Connect the three internal battery conne...

Страница 66: ...d Tighten the thumbscrew on the right battery retention bracket 4 10 Reinstall the left battery retention bracket a Slide the left battery retention bracket to the right and into the slot 1 OK OK 100...

Страница 67: ...11 To attach the UPS lower front bezel press the two side latches toward each other align the bezel with the UPS and snap it into place OK OK 100 6 min Chapter 5 Hardware maintenance information 53...

Страница 68: ...y Test 4 Press the OK button to view the Battery Test status Note If the battery test is already scheduled or running you can choose to cancel the test If the previous battery test failed or did not c...

Страница 69: ...information from two main menus on the display v UPS status Access to all active alarms and battery data v Alarm history Access to the most recent 50 events which might include active and closed alarm...

Страница 70: ...listed events notices and alarms Serial connection to a computer Through a serial connection you can access the last 50 events notices and alarms that are recorded in the UPS alarm history The events...

Страница 71: ...with a list of events that includes the event type ID date and time and name For example Alarm 199 03 10 2010 10 55 38 Battery Disconnected Notice 025 03 09 2010 08 30 40 Output Overload Event 181 03...

Страница 72: ...terrupted One of the conditions listed in Running automatic battery tests on page 41 was not present Resolve the condition and then restart the test In High Efficiency Mode Event 227 No alarm The UPS...

Страница 73: ...ing was detected during the last battery test This is a warning notice Replace the batteries soon Service Battery Alarm 149 Fast Beeping Alarm A faulted battery string has been detected and as a resul...

Страница 74: ...representative Inverter AC Over Voltage Alarm 0 Fast Beeping Alarm The UPS has detected abnormally high output voltage levels The UPS transfers to Bypass mode if supporting the load Inverter AC Under...

Страница 75: ...functioning correctly This is an alarm only Contact your service representative immediately and remove the load Bypass AC Over Voltage Notice 3 Slow Intermittent Alarm The measured voltage on Bypass...

Страница 76: ...62 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...

Страница 77: ...ions of error messages and error codes If you suspect a software problem see the documentation for the operating system or program Using the documentation Information about your IBM system and preinst...

Страница 78: ...378 Hardware service and support You can receive hardware service through your IBM reseller or IBM Services To locate a reseller authorized by IBM to provide warranty service go to http www ibm com pa...

Страница 79: ...SS FOR A PARTICULAR PURPOSE Some states do not allow disclaimer of express or implied warranties in certain transactions therefore this statement may not apply to you This information could include te...

Страница 80: ...el volume KB stands for 1024 bytes MB stands for 1 048 576 bytes and GB stands for 1 073 741 824 bytes When referring to hard disk drive capacity or communications volume MB stands for 1 000 000 bytes...

Страница 81: ...Limits Particulate v The room air must be continuously filtered with 40 atmospheric dust spot efficiency MERV 9 according to ASHRAE Standard 52 21 v Air that enters a data center must be filtered to...

Страница 82: ...adio or television interference caused by using other than recommended cables and connectors or by unauthorized changes or modifications to this equipment Unauthorized changes or modifications could v...

Страница 83: ...ortung f r die Einhaltung der Schutzanforderungen wenn das Produkt ohne Zustimmung der IBM ver ndert bzw wenn Erweiterungskomponenten von Fremdherstellern ohne Empfehlung der IBM gesteckt eingebaut we...

Страница 84: ...onment radio interference may occur in which case the user may be required to take corrective actions Japan Electronics and Information Technology Industries Association JEITA statement Japanese Elect...

Страница 85: ...People s Republic of China Class A electronic emission statement Taiwan Class A compliance statement Appendix B Notices 71...

Страница 86: ...72 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...

Страница 87: ...tion 31 controlling load segments through LCD 38 Converter mode 29 CRU listing 47 D danger statements 6 disconnecting internal battery 22 UPS and extended battery module 13 display function alarm hist...

Страница 88: ...software installing 43 R rack installation 10 rear view extended battery module 10 rear view controls and power 9 remote emergency power off connecting a switch 15 connectors 14 overview 14 replaceabl...

Страница 89: ...PS Manager software 43 load segments 38 models 1 network management card 45 rear view controls and power 9 replaceable components 47 replacing battery module qualified personnel only 48 RS 232 port 44...

Страница 90: ...76 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...

Страница 91: ......

Страница 92: ...Part Number 60Y1454 Printed in USA 1P P N 60Y1454...

Отзывы: