Address Name

Designation

Data 
form

Read/
Write

Factor Unit

10

Current rotor 
speed

Only calculated if the speed 
reference value remains constant 
between two pulses on the 
rotation monitor. Displays 0 if no 
value is available. 

To ensure the correctness of 
the measured value the speed 
reference value should be 
changed. This will cause the 
registry to read as 0 until the 
current value is displayed.

UINT 16 Read

100

rpm

11

Fault registry

Read integer equals a fault code 
generated in Sub-faults,  
address 33-52.

UINT 16 Read

12

Fault registry 

Reads 1 if VariMax has tripped.

UINT 16 Read

13

Fault registry

Read value equals a 16-bit integer 
where the bit numbers match 
fault codes that are on addresses 
1-16 in Discrete Input.

UINT 16 Read

14

Fault registry

Read value equals a 16-bit integer 
where the bit numbers match 
fault codes that are on addresses 
17-23 in Discrete Input.

UINT 16 Read

15

Fault registry

Read value equals a 16-bit integer 
where the bit numbers match 
fault codes that are on addresses 
33-48 in Sub-faults.

UINT 16 Read

16

Fault registry

Read value equals a 16-bit integer 
where the bit numbers match 
fault codes that are on addresses 
49-52 in Sub-faults.

UINT 16 Read

Continued from previous page

24

25

Содержание VariMax100M

Страница 1: ...IBCcontrol Made in Sweden MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER WITH MODBUS VariMax100M UL CSA Article no F21100304...

Страница 2: ......

Страница 3: ...utton 8 Connection diagram 9 Connections 9 Input signal Rotation speed 10 Checks before powering up the control unit 10 Commissioning the equipment 10 EMC installation 11 EMC gland 11 Modbus 13 Techni...

Страница 4: ...sal and recycling When replacing components or when the control unit in its entirety needs replacing please follow the advice below The aim shall always be to achieve the maximum possible recycling of...

Страница 5: ...h off main power before removing the cover Never touch electrical components or contacts while main current is switched on Risk of electrocution resulting in serious injury or death Connected terminal...

Страница 6: ...800 3 2004 emission category C1 and immunity category C2 All control units comply with the Low Voltage Directive 2006 95 EC standard EN 61800 5 1 All control units are designed for installation in env...

Страница 7: ...signal shift which means that the rotor s efficiency is proportional to the input signal The VariMax100M has a preset threshold value of 0 1 V hysteresis 0 13 0 07 V If the input signal falls below t...

Страница 8: ...e 4 AT Exact value cannot be obtained with a digital measuring instrument The fuse protects both motor and electronics TECHNICAL DATA CONTROL UNIT Max moment 10 Nm Min rotation speed 1 rpm Max speed R...

Страница 9: ...e rotation sensor DIP switch setting Flashes even if the input signal is lower than the threshold value ALARMS In the event of an alarm the control unit restarts after 30 seconds The respective red li...

Страница 10: ...level 85 30 O C Short circuit Probable cause Alarms and trips in the event of short circuit phase phase or phase earth Short circuit between phases in cable or motor Short circuit between phase earth...

Страница 11: ...to terminal 10 The magnet is installed with south side S towards the transmitter Max gap 15 mm 12 V output 3 11 Output for 12 V DC Terminal connection 3 is minus terminal connection 11 is plus Max 50...

Страница 12: ...position Adjust Max rpm so that the rotor rotates at 10 12 rpm or as per rotor manufacturer s directions Checking minimum speed Set the Low Speed DIP switch to ON Check that the rotor starts The mini...

Страница 13: ...HAR UL CSA 7G0 75 Shielded Input signal LiYCY 2x0 34 0 5 UL recognized Shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EMC Directive...

Страница 14: ...12...

Страница 15: ...13 M o d b u s...

Страница 16: ...14...

Страница 17: ...parity 8 databits 1 stop bit no parity 8 databits 2 stop bits no parity 8 databits 1 stop bit odd parity Address 8 unique addresses refer to the table Addressing page 18 Termination Embedded terminal...

Страница 18: ...peed on page 8 Resetting Resetting can be made via Modbus via the Reset button or via Remote Reset Refer also to Resetting on page 8 and Remote Reset on page 9 Input signal This is controlled via Modb...

Страница 19: ...Indication of communication error Steady red Not connected to the bus Connected to a bus without traffic Incorrect address set via the DIP switch In the event of no data if the reference value is rece...

Страница 20: ...0 0 11 17 1 0 0 28 40 0 1 0 29 41 1 1 0 90 144 0 0 1 91 145 1 0 1 A8 168 0 1 1 A9 169 1 1 1 Rate 9 600 0 0 19 200 1 0 38 400 0 1 56 000 1 1 Package 1 stop bit even parity 0 0 1 stop bit no parity 0 1...

Страница 21: ...ite 1 to activate the rotation monitor or 0 to deactivate Single bit Read Write 4 Manual speed Write 1 to activate manual speed instead of the control signal from Modbus If the function is activated v...

Страница 22: ...re in the control unit Single bi Read 5 Overheating AC Overheating in the control unit Single bit Read 6 Under voltage AC Low supply voltage Single bit Read 7 Voltage surge AC High supply voltage Sing...

Страница 23: ...bit Read 22 Short circuit Motor impedance high Incorrect motor impedance e g incorrect size of motor failed motor or bad connections Single bit Read 23 Internal fault Internal fault regardless of typ...

Страница 24: ...imeout when calibrating current shunts Single bit Read 43 Internal fault Under voltage intermediary Single bit Read 44 Internal fault Excess voltage intermediary Single bit Read 45 Internal fault Not...

Страница 25: ...control unit INT 16 Read C 5 AC voltage Supply voltage for VariMax UINT 16 Read V 6 Operating mode Source for speed reference value s in current use 1 Low speed DIP switch ON 2 High speed DIP switch O...

Страница 26: ...INT 16 Read 12 Fault registry Reads 1 if VariMax has tripped UINT 16 Read 13 Fault registry Read value equals a 16 bit integer where the bit numbers match fault codes that are on addresses 1 16 in Dis...

Страница 27: ...32 Read 44 Modbus packets Number of faulty packets in Modbus UINT 32 Read 46 Total operating time Total operating time for the control unit UINT 32 Read s 48 Fault waiting time Time with an active fa...

Страница 28: ...unction 06 Write Singles Registries is used for Writing Continued from previous page Address Name Designation Data form Read Write Factor Unit 56 Stop time normal temp Time with stopped motor 0 40 C U...

Страница 29: ...27 OWN NOTES...

Страница 30: ...OWN NOTES 28...

Страница 31: ...OWN NOTES 29...

Страница 32: ...IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Tel 46 0 42 33 00 10 Fax 46 0 42 33 03 75 www ibccontrol se info ibccontrol se IBCcontrol F21100904GB VERSION 1 2017 01 04...

Отзывы: