background image

7

DIP SWITCH

Cleaning function

Cleaning function connected in ON position. When the rotor has stopped 
for 10 minutes, the cleaning function is activated and the rotor starts to 
rotate. As a warning, the rotor first rotates for 6 seconds at a motor speed 
of 5 rpm, the rotor is then stationary for 3 seconds. After this, the actual 
cleaning starts, for a random time, between 10 to 20 seconds with the 
motor at 20 rpm.

Rotation monitor

Rotation monitor connected in ON position.

High speed *)

The rotor rotates at the set max. rpm when the switch is set to ON.

Low speed *)

The rotor rotates at the preset min. speed (1 rpm) when the switch is set 
to ON.

 *) Manual operation (test mode)

OPERATIONAL INDICATIONS

On/Alarm

"Voltage on" comes on with a fixed light. 
Flashes when the control unit has tripped.

Run

Comes on when the motor is to rotate, i.e. when the input signal exceeds 
the threshold value.

Rotation

Flashes when the magnet passes the magnetic sensor, regardless of the 
rotation sensor DIP switch setting. 
Flashes even if the input signal is lower than the threshold value.

ALARMS

In the event of an alarm the control unit restarts after 30 seconds. The respective red light diode comes 
on for the same duration (30 seconds).  
After restart the light diode goes out, this happens twice. The third time, the alarm relay closes and the 
alarm "moves on". 
In order for the alarm relay to close and the alarm to "move on", the above three alarm signals must 
occur within 90 minutes, otherwise the sequence is reset. 
A steady green LED is activated for the first and second alarm and begins to flash on the third alarm.  
All alarms subsequently remain active.  

Rotation monitor

Generates an alarm and trips if a pulse has not been received every 30 
minutes at minimum speed (1 rpm) and every 20 seconds at maximum 
speed (375 rpm). 
The time between these speeds is linear. 
The function can be disconnected via DIP switches.

Continued on next page

Содержание F21050303

Страница 1: ...IBCcontrol MANUAL CONTROL UNIT FOR ROTARY HEAT EXCHANGER VariMax50 UL CSA Article no F21050303 M ade in S w ed en Since 1983 Since 1983 Ska vara 25 mm i diameter p h jden...

Страница 2: ......

Страница 3: ...cal data control unit 6 Technical data motor 6 Functions 6 DIP switch 7 Operational indications 7 Alarms 7 Settings via potentiometer 8 Push button 8 Connection diagram 9 Connections 9 Input signal Ro...

Страница 4: ...sal and recycling When replacing components or when the control unit in its entirety needs replacing please follow the advice below The aim shall always be to achieve the maximum possible recycling of...

Страница 5: ...h off main power before removing the cover Never touch electrical components or contacts while main current is switched on Risk of electrocution resulting in serious injury or death Connected terminal...

Страница 6: ...immunity category C2 All control units comply with the Low Voltage Directive 2006 95 EC standard EN 61800 5 1 All control units are designed for installation in environments subject to pollution degre...

Страница 7: ...oportional to the input signal The VariMax50 UL CSA has a preset threshold value of 0 1 V hysteresis 0 13 0 07 V If the input signal falls below this value the rotor will stop The VariMax50 UL CSA has...

Страница 8: ...suring instrument The fuse protects both motor and electronics Note The control unit must be connected to power all the time TECHNICAL DATA CONTROL UNIT Max moment 4 Nm Min rotation speed 1 rpm Max sp...

Страница 9: ...eds the threshold value Rotation Flashes when the magnet passes the magnetic sensor regardless of the rotation sensor DIP switch setting Flashes even if the input signal is lower than the threshold va...

Страница 10: ...85 30 O C Short circuit Probable cause Alarms and trips in the event of short circuit phase phase or phase earth Short circuit between phases in cable or motor Short circuit between phase earth in cab...

Страница 11: ...wn to terminal 10 The magnet is installed with south side S towards the sensor Max gap 15 mm 12 V output 3 11 Output for 12 V DC Terminal connection 3 is minus terminal connection 11 is plus Max 50 mA...

Страница 12: ...sition Adjust Max rpm so that the rotor rotates at 10 12 rpm or as per rotor manufacturer s directions Checking minimum speed Set the Low Speed DIP switch to ON Check that the rotor starts The minimum...

Страница 13: ...HAR UL CSA 7G0 75 Shielded Input signal LiYCY 2x0 34 0 5 UL recognized Shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EMC Directive...

Страница 14: ...OWN NOTES 12...

Страница 15: ...OWN NOTES 13...

Страница 16: ...IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Tel 46 42 33 00 10 www ibccontrol se info ibccontrol se IBCcontrol F21050903GB VERSION 1 0 3 2020 04 28...

Отзывы: