SL 40-399 G3 - Convert to LP fuel (P-Kit 302B)

|

7

Where to Place Conversion Labels on the Boiler

 

Содержание SL 40-399 G3

Страница 1: ...owed exactly a fire an explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agency is responsible for the proper installa...

Страница 2: ...eft of the long brass protrusion on the front of the gas valve It will have to be adjusted to attain optimum combustion results whenever fuel conversion is undertaken however no mixture adjustment mus...

Страница 3: ...e the O ring and orifice if installed You will need the O ring in Step 8 4 Note the orientation and screw positions and then remove the bolts and venturi mixing device from the fan 5 Remove the ventur...

Страница 4: ...Errors The boiler automatically resets after 60 minutes if no action is taken To perform a combustion test and adjustment 1 Turn off the boiler s gas shut off valve 2 With a small 1 8 or 3 mm flat scr...

Страница 5: ...grammed settings will be restored and the load will operate as before Confirm a smooth ignition sequence 12 Turn off the gas supply at the gas shut off valve 13 Disconnect the power to the boiler 14 D...

Страница 6: ...shut off 4 With a Stop Watch record the number of seconds for the smallest dial to make 1 full revolution 5 CFH 3600 x Dial Size Seconds 6 CFH x 1000 check local Btu content Input Btu s Note For 2 PS...

Страница 7: ...SL 40 399 G3 Convert to LP fuel P Kit 302B 7 Where to Place Conversion Labels on the Boiler...