IBC SFC Скачать руководство пользователя страница 23

1-19

BOILER SYSTEMS AND OPERATION

CONTROLLER MANUAL – SFC/SFB SERIES BOILERS

The SF series units include a factory installed and pre-wired pump. The pump 

may not be able to supply adequate flow for the heat emitter circuits. A system 

heating pump switched through a separate relay or control box may be needed.

SEQUENCE OF OPERATION

The boiler operates in a similar way for both a space heating and a domestic hot 

water call for heat. When the boiler is powered up the controller enters a self-

diagnostic mode, and displays “2” in the Service Display.
The Sequence of Operation is as follows:

1 .

  The boiler receives a call for heat from closing terminals X13.1 and X13.2 

(24 volts section). The boiler can also receive a call from Domestic Hot Water 

heating from the internal flow sensor, or from a 10KΩ sensor or aquastat 

(X13.4 and X13.5 in 24V terminal).

2 .

  The boiler does a safety check and energizes the fan for a pre-purge  

(

Service Display = 3

).

3 .

  Once the 5-second pre-purge is compete, the boiler enters a 5-second trial 

for ignition (

Service Display = 4

).  If the boiler fails to ignite, the boiler will 

complete a 5-second inter-purge then another 5-second trial for ignition.  This 

is repeated 4 times before a hard lock-out occurs. The Return button must be 

pressed to reset the controller and to allow for another attempt.

4 .

  Once the burner is lit and flame has been proven the boiler operates as it is 

programmed (

Service Display

 =   for Space Heating or 

for Domestic 

Hot Water).

5 .

  If the boiler reaches its target temperature and there is still a call for heat 

or hot water the Burner will turn off (integral pump runs unless call is on-

demand dhw ). (

Service Display = 1

)

6 .

  After the call for heat is satisfied, the boiler pump will operate for an 

adjustable amount of time (

Service Display = 0

).

7 .

  If the burner is on to maintain the heat exchanger temperature for DHW 

Comfort mode or for Freeze Protection mode (

Service Display = 7

).

8 .

  If the burner is on to maintain the heat exchanger temperature for DHW 

Comfort mode or for Freeze Protection mode (

Service Display = 7

).

Содержание SFC

Страница 1: ...CONTROLLER MANUAL www ibcboiler com SFC SFB Controller Visitez galement notre site web www ibcboiler com TIPortal pour y obtenir ce manuel en fran ais...

Страница 2: ...G If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life WARNING Points out a potentially hazardous situation...

Страница 3: ...RE 1 5 ADJUSTING THE DHW TEMPERATURE 1 6 CHECKING THE DHW FLOW 1 7 ADJUSTING THE DHW MODES 1 7 ACCESSING THE SERVICE MENU 1 8 Testing the unit firing rate 1 9 ACCESSING THE INFORMATION MENU 1 10 ACCES...

Страница 4: ...Installation Code CAN CSA B149 1 as applicable Failure to correctly install and operate this appliance can result in severe personal injury or death The water heater shall have a pressure relief valve...

Страница 5: ...er operational status Other indicators enable you to program the boiler INTERFACE INDICATORS BUTTONS ICON FUNCTION A Numerical Display Main Display B Plus Minus Temperature Adjustment C Flame Burner O...

Страница 6: ...readings and other operating conditions Service menu Use to view service information access the Installer menu to change parameters In this menu you can view service information and regulate the firin...

Страница 7: ...a heat demand The unit is turned on and is ready to respond to a request for domestic hot water or space heating In this mode the display view shows the Dot The unit is in operation and is supplying...

Страница 8: ...CONTROLLER MANUAL 1 4 CONTROLLER MANUAL SFC SFB SERIES BOILERS This page is intentionally left empty...

Страница 9: ...cess the Information menu to obtain information on displayed codes ADJUSTING THE SPACE HEATING WATER TEMPERATURE To adjust the water temperature in the space heating 1 From the Main menu touch the Spa...

Страница 10: ...display 2 To change the DHW target temperature touch the Plus or Minus buttons 3 To save the changes touch the Return button To exit without saving the changes touch the On Off button NOTE The boiler...

Страница 11: ...at exchanger temperature Standard Mode OFF The unit will respond to a call for DHW as a priority over the space heating demand When the DHW demand is satisfied the unit will return to the space heatin...

Страница 12: ...f the screen indicates that the changes have been saved To exit without saving the changes touch the area above the Dot ACCESSING THE SERVICE MENU The Service Menu provides service information and con...

Страница 13: ...us at the same time A L will display on the right Program h Burner on with maximum Space Heating setting With a call for heat press Wrench and Plus at the same time An h will display on the right Prog...

Страница 14: ...n for two seconds The Minus Plus Wrench and Enter indicators are displayed 3 Again touch and hold the Wrench button for two seconds You are now in the Information menu Note that the Enter button has d...

Страница 15: ...TO CHANGE CONTROLLER PARAMETERS The Installer Menu allows installers to change controller parameters set out in table 3 on pages 1 13 to 1 16 You can access these parameters through the installer s c...

Страница 16: ...to open the parameter for editing You can use the Plus or Minus buttons to choose a different parameter Multiple changes can be made and all will be saved when the Return is pressed P to the right of...

Страница 17: ...tank Tank differential 9 F 5 C 5 Combi External directly heated tank Tank differential 9 F 5 C P003 Units 1 0 Metric C L S Bar 1 Imperial F gpm PSI P010 Maximum Space Heating Output SFC 125 75 All oth...

Страница 18: ...Design Supply Temperature 176 F 80 C 50 F to 194 F 10 C to 90 C P052 Design Outdoor Temperature 16 F 9 C 22 F to 50 F 30 to 10 C P053 Summer Shutdown Temperature 77 F 25 C 50 F 85 F 10 C 30 C P056 Min...

Страница 19: ...al tank set temperature unit C 140 F Table 3 Information codes Smart outdoor reset function When using a non modulating room thermostat on off if no outdoor reset sensor is connected to the boiler it...

Страница 20: ...CONTROLLER MANUAL 1 16 CONTROLLER MANUAL SFC SFB SERIES BOILERS This page is intentionally left empty...

Страница 21: ...ump a DHW pump and an outlet for unit power A certified harness from the wiring box connects to the movable controller tray You do not require a junction box if 1 the unit s integral pump provides ade...

Страница 22: ...bonded to ground in accordance with the requirements of the authority having jurisdiction or in the absence of such requirements with the National Electrical Code ANSI NFPA 70 and or the Canadian Elec...

Страница 23: ...rvice Display 3 3 Once the 5 second pre purge is compete the boiler enters a 5 second trial for ignition Service Display 4 If the boiler fails to ignite the boiler will complete a 5 second inter purge...

Страница 24: ...rge XXX 1 Boiler water temperature reached target boiler pump is energized call for heat still present XXX 2 Self test When power is applied to the boiler the controller enters a self diagnostic mode...

Страница 25: ...y Check for the correct operation of heating supply temperature sensor S1 Replace the heating supply temperature sensor S1 F002 Temperature too high during DHW demand Check wiring of domestic hot wate...

Страница 26: ...fault S3 Domestic hot water sensor S3 is not mounted correctly Mount the sensor correctly F018 Flue and or air supply duct is blocked Check the flue and the air supply duct Clean the flue and or the...

Страница 27: ...Revision History R0 JUNE 2019 Initial release R1 NOVEMBER 2019 Minor changes R2 MARCH 2020 Changes to parameters including new feature Smart Outdoor reset function parameter P061...

Страница 28: ...J 5M8 Toll Free 1 844 432 8422 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 318 R2 84105402 March 2020 IBC Technologies Inc 2020 IBC Technologies USA Inc 1702 Taylors Lane Cinnaminson NJ 08...

Отзывы: