How to Install the P-749 Controller

1.  Retrieve and record any settings desired from the old controller, if possible.  Enter Installer 
Setup mode as per step 13 below.  Settings can be recorded in the column provided in Fig. 3. 

2.  Remove any call for heat, and remove power from the boiler / water heater. 

3.  Remove cabinet front door panel.  

4.  Pull forward the bottom tray which holds the controller.

5.  Disconnect the electrical connections from the old board: the three white plugs require 
unlatching their clips to be lifted out.  The green terminal strips can be removed by pulling 
upward.  Needlenose pliers are recommended for removing the five ground connectors.  

6.  Note that the entire tray can now be easily removed from the boiler if desired.  Undo and 
set aside for re-use the two Phillips screws on the underside of the controller tray.  Remove old 
controller from tray.

7.  Place the replacement board in the original board’s position, so buttons are centred in their 
holes and mounting holes align.  Install the two screws for the board chassis.  Confirm that the 
front panel buttons engage with the new controller (you should feel and hear that the buttons 
click when pressed).

8.  Reinsert boiler tray if necessary.  Attach the grounding wires, terminal strips and plugs as 
the original board was wired.  Make sure plugs are fully engaged.

9.  Close the tray, power up the board and wait ten seconds.  The board will display dashes.  

10.  Press the service button [wre and the reset buttons con] simultaneously to get zeros in the 
Main and Service windows.  Press the button below the main window repeatedly until a “25” 
is displayed.  Press the service button            once to enter Model Setup menu.  

11.  The main window will display “PA”; by pressing the + button, choose the appropriate PA 
type according to the model of the boiler.  See Figure 2.  Save the choice by pressing the Reset  
button         .  A “P” will display for about 5 seconds.

12.  The boiler controller is now set up for the correct model.  The final step will be to enter 
operational parameters in the User and Installer menus.  The user menu is accessible simply by 
pressing the Thermometer icon     for two seconds.  The LED by the radiator icon         indicates 
the +/- buttons can be used to adjust the Space Heating water temperature (see publication 
DC /HC Controller Manual for more information).  Toggle to enter the DHW temperature setup. 
Saving changes is done by pressing the Reset button        .

13.  Enter the Installer menus by pressing the service on]   and the reset buttons [on] 
simultaneously to get zeros in the display windows. Press the + button until a “15” is displayed 
in the Main window.  Press the service button           to enter Parameter 1, System Type.  See 
Figure 3 for a complete list of parameters.  A column is provided for the Installer to record 
settings.  Use the service button            to scroll through the parameters, the +/- buttons to 
adjust values, and the Reset button         to save all changes.  If further information is required 
see the IBC publication DC / HC Controller Manual.

Note: after installation, upon powering up the boiler, the board will briefly display r 2.10 and a PA x-.  
This is the software revision number and the first digit of the selected PA type .

           

Better 
Boilers 

INSTRUCTIONAL 
NOTE

P-749 Controller Replacement Kit

DC / HC Series (All Models)

Figure 2: Parameter 
Types by Model 

PA 46

DC 33-124

PA 45

HC 33-124

PA 44

DC 29-106

PA 43

HC 29-106

PA 42

DC 23-84

PA 41

HC 23-84

PA 31

HC 13-50

PA 22

DC 33-160

PA 21

HC 33-160

PA 12

DC 20-125

PA 11

HC 20-125

PA 62

DC 15-96

PA 61

HC 15-96

PA 52

DC 15-95

PA 51

HC 15-95