IBC P-242B V-10 Скачать руководство пользователя страница 4

IBC Technologies Inc.

1-844-432-8422

|

www.ibcboiler.com

120-199E4

July 31, 2023

Released Document

4 of 6

Figure 1

Figure 2

3. Carefully lift the controls off both mounting plates. Proceed to

Installing Replacement Touchscreen

Controller on page 4

Installing Replacement Touchscreen Controller

1. Install the replacement controller as directed in the table below:

For swing-
out style
controllers:

a. Place the replacement screen control onto the swing-out door style control

mounting plate, and reinstall the 5 screws. Avoid over-tightening the screws.

b. Plug the connectors into the back of the board.

For CX
Controllers:

a. Ensure that the CBI control board is secured to the replacement control

module.

b. Place the replacement touchscreen control module onto the swing-out door

style control mounting plate, and reinstall the 5 screws. Avoid over-tightening
the screws.

c. Install retained connector bracket and screw; do not over-tighten the screw.

d. Install the retained two screws that secure the CBI control board to the back

chassis.

For older
IBC boiler
models with
fixed
controllers:

a. Remove the front cover from the new controller.

b. Support the board as you plug the four connectors into the back of the board.

c. Screw the back-plate of the controller to the cabinet of the boiler using the

four screws previously removed with the old controller.

d. Replace the new front cover of the controller.

Table 1: Installing Replacement V10 Touchscreen Controller

Отзывы: