background image

We recommend that you always use a primary/secondary piping 

configuration (see below for a basic configuration).

In the case of hard water, use distilled or purified water. Glycol 

systems require the use of propylene glycol. For large volume 

systems, the optimum hardness is ≤2 grains.

Water Chemistry Allowable Limits

Acidity pH

6.6 - 8.5

Chloride

< 125 mg/l

Iron

< 0.5 mg/l

Copper

<0.1 mg/l

Conductivity

<

400μS/cm (at 25°C)

Water Hardness

7 Grains

• 

Place an air separator at the highest point. These 

must be 

installed above each boiler

.

• 

Install the pressure relief valve in a vertical position. Do not 

use an isolation valve between the boiler and relief valve.

• 

Support all piping with appropriate piping brackets.

• 

Plumb an appropriately sized expansion tank and make up 

the water station into a fitting on the suction side of the 

circulator. 

• 

Size boiler piping and pumps for the BTU output of the boiler.

For non-oxygen barrier piping systems, use a dirt separator and/

or a side stream filter. Ensure that the system is free of iron 

components, and treat with an inhibitor. 

Electrical

 

(Section 3.10

)

1.  Connect the boiler to a dedicated (max.)15 Amp breaker.
2.  Wire the AC to the black and white wires labeled in the 

Field wiring box.

3.  Ensure that the boiler is properly bonded (grounded).
4.  Refer to the “Wiring Diagrams” section in the 

Installation 

and Operating Instructions

 manual (Fig 42) for more 

information.

5.  Wires labelled “Boiler Pump:” Wire power for the boiler 

pump to the black wire, and the boiler pump “L” (hot) 

connection to the yellow wire.

6.  Wire the respective load pumps into the TB1 Terminal; for 

example, PV 1, 2, 3, 4.

Electrical

 continued 

(Section 3.10

)

Water Piping 

(Section 3.8)

1.  Wire thermostats or end switch dry contacts to Therm 24 

Vac, and then connect the other wire to Therm 1, 2, 3, 4 

corresponding to the load pump PV1, 2, 3, 4.

2.  For a DHW load, wire either an Aquastat to the appropriate 

Therm. connection or a 10K Ω type II/B curve thermister to 

the DHW Sensor connection.

The boiler requires proper grounding, which conforms to all 

electrical codes, ensuring proper flame rectification.

• 

For multiple-boiler setups, use a secondary loop sensor wired to 

the Master boiler.

• 

For zone valves or external peripherals, use external 

transformers.

Note:

 

If a load is defined as Reset Heating, the outdoor sensor 

must be used for proper operation. 

Express Setup

1.  On theV-10 Touchscreen controller, tap the 

Home

 (Standby) 

screen>

Main Menu>Express Setup

.

2.  Do the following:

a.  Tap the 

Enter Design Outdoor Temperature

 box, and 

enter a value.

b.  Tap 

Set Clock

 to set the time and date.

c.  Tap 

Save

.

3.  Select a load and then select the load type.
4.  Accept the defaults, or change any of the settings.
5.  You can find more substantial settings in "Installer Settings".
6.  Tap the 

Save

 button. 

Manual Pump Purge

After the system is pressurized and you have defined loads, 

perform a manual pump purge to ensure air is purged.
On the touchscreen controller, go to 

Main Menu

Installer 

Settings

System Settings

 > 

Site Settings

>Set 

Manual Pump 

Purge to 

"

ON

">

OK

>

Save.

The manual pump purge runs until it is turned off, or when there 

is a call for heat.

Checklist

Treated water or Polypropylene glycol mixture in the pipes.

Boiler system is pressured and flushed ≥ 8 psi.

All gas connections soap-tested for leaks and now leak free.

Voltage supply to the boiler tested for voltage (nominal 120 
Vac), polarity, and properly grounded.

The boiler requires a dry set of contacts in the Therm 
connections.

Boiler power turned on.

Reset low gas pressure switch

Use the “Express Setup” in the touchscreen controller to set 
up the required loads. See above for instructions.

Steps followed in the “6.3 Commissioning” section of the 

Installation and Operating Instructions

 

manual.

Completed the Installation & Commissioning Report in the 

Installation and Operating Instructions manual - Combustion 

Readings recorded.
CO

2

_________

_

 % O

2

 ________ % CO _______ppm

1.  Pressure relief valve (shipped with boiler): no isolation valve 

permitted between boiler and relief valve 

2.  Tridicator (shipped with boiler) 
3.  Microbubble air eliminators 
4.  Expansion tank connection 
5.  Boiler Pump 
6.  Closely-spaced tees to/from Load 1 
7.  Closely spaced tees to/from  Load 2 
8.  Fill station 
9.  Dirt seperator recommended

Отзывы: