background image

EX Series Quick Reference Installation Guide

Boiler Mounting 

(

Section 3.0 of the manual

)

Venting 

(Sections 3.5)

Gas Supply 

(

Section 3.9

)

Follow the venting specifications and information for the correct venting 

material and venting length provided in the above sections of the 

manual.

 

Ensure that sidewall configurations have adequate vertical separation, 

and that exhaust plumes are well away from all building air intake vents.
Ensure that all venting material is sloped towards the boiler at 

a minimum of ⅝″ per foot or at a slope required by the PP vent 

manufacturer, whichever is greater.
Ensure that PPs venting is supported every 36″ (min).
On longer horizontal runs of PVC and CPVC, increase the grade to ⅜″ or 

more.
Fully insert the approved venting material into the boiler’s exhaust 

outlet, and tighten the clamp to ensure 

the venting connection is locked in 

place.
Check that the venting is securely 

attached to the exhaust flue of the 

boiler by pulling on the venting. 

Important:

 

Use appropriate appliance adapters when using PPs 

or stainless steel venting.

Condensate Trap 

(

Section 3.6

)

1.  Fill the trap assembly with water.
2.  Attach the trap to the drain elbow.
3.  Tighten the union nut.
4.  Check for leaks.

For gas delivery to the boiler, we recommend using hard piping 

rather than flexible piping. If you use flexible piping, ensure that 

the gas pipe size is appropriate for the maximum BTU input of 

the boiler.

Minimum Gas Pressure

4" w.c.

Maximum Gas Pressure

14" w.c.

Size piping for sufficient sustained gas delivery at sufficient 

pressure to the boiler.

Recommended Supply Pressure at Full Load

Natural Gas

7"

Propane

10"

• 

Ensure that there is a minimum of 6 feet of piping between 

the boiler and gas regulators. 

• 

Use a manometer to test that gas delivered to the boiler is 

delivered at sufficient pressure and that “lock up” does not 

exceed the maximum pressure.

• 

If using a 5 psi to inches vented gas regulator, always oversize 

the vent pipe to prevent hunting of the gas regulator when 

boilers are firing at lower output levels.

In retrofits with existing copper gas pipes, clean and clear the 

gas piping of any debris before connecting to the boiler. Failure 

to do so can result in a blocked gas valve and inconsistent 

performance.

Maximum Pipe 

Length by Model

l

 

IPS

1 ½

 

IPS

2

 IPS 2 ½

 

IPS

EX 400 

(Natural Gas)

150’

350’

1000’

>2000’

EX 400 

(Propane)

400’

900’

>2000’ >2000’

EX 500 (Natural Gas)

100’

200’

700’

1800’

EX 500 (Propane)

250’

600’

2000’

>2000’

EX 700 

(Natural Gas)

50'

100'

350'

800'

EX 700 (Propane)

150'

300'

900'

2000'

EX 850 (Natural Gas)

40'

80'

250'

600'

EX 850 (Propane)

100'

200'

700'

1600'

LWCO Errors 

To clear LWCO errors caused by air:
1.  Ensure that there is no air trapped in the boiler and 

boiler piping.

2.  On the touchscreen controller Main Menu, go to 

Diagnostics

Advanced Diagnostics

Clear System 

Errors

Yes

OK

.

Ensure that the boiler’s anchor brackets are securely bolted to the 

floor.

QS003  Quick Reference Installation Guide - EX 400, 500, 700, EX 850

Important:

 

Before turning off the boiler, make sure it is in 

“Standby” mode.

Low Gas Pressure Errors 

(

Section 6.3.5

)

Every new install will require resetting the low gas pressure 

switch. To do so, press on the red reset button.

Important:

 

Not applicable for construction heating. Fouled fans, 

burners, and ignitors are not covered under warranty.

Low gas 

pressure 

switch

High gas 

pressure 

switch

Maximum Exhaust Venting Lengths

Exhaust Pipe Size

EX 400, EX 500

EX 700, EX 850

Sched.40; Rigid PPs
4" PVC/CPVC / Rigid PPs/SS

170' (each side)

n/a

6" PVC/CPVC / Rigid PPs/SS

 n/a

120' (each side)

90° vent elbow

allow 5' equivalent allow 5' equivalent

45° elbow

allow 3' equivalent allow 3' equivalent

PPs 87-90° elbows

use 5' equivalent

use 5' equivalent

Отзывы: