Supply / Return Air Trunk Size CFM at .3"wc external static pressure (galvanized duct)
Round
Rectangular
CFM range
8"
8 x 6
8 x 7
160-190
190-230
9"
8 x 8
230-275
10"
10 x 8
275-360
11"
12 x 8
360-460
12"
14 x 8
460-570
13"
16 x 8
570-650
13"
18 x 8
650-750
14"
20 x 8
750-850
14"
22 x 8
850-950
15"
24 x 8
950-1050
Table 6
Supply air trunk size CFM at galvanized duct .3"wc ESP for return and supply air
2.3.2 Ducting installed in conditioned space
If a cooling system is connected to the appliance, we recommend insulating the supply air ducting with
a minimum of 1" thick fiberglass insulation with a vapor barrier. All insulated joints must be sealed with
tape designed for this purpose.
2.3.3 Ducting installed in un-conditioned spaces
Supply air and return air ducting should be insulated with a minimum 2" thick fiberglass insulation with a
vapor barrier. All insulated joints must be sealed with a tape designed for this purpose.
2.3.4 Making the return air openings
Both sides as well as the bottom of the appliance provide markings for the maximum return air opening.
Use suitable metal cutters to perforate the marked area for the return air supply. Ensure that you cut
within the marked area.
27
2.3.2 Ducting installed in conditioned space
Содержание AHU Series
Страница 1: ...INSTALLATION OPERATING MANUAL Air Handling appliances AHU 800 AHU1200 AHU 1600...
Страница 2: ......
Страница 5: ...5 3 Fault Codes 67 Air handling appliance parts diagram 70 3...
Страница 6: ...This page is intentionally left blank...
Страница 18: ...This page is intentionally left blank...
Страница 60: ...This page is intentionally left blank...
Страница 68: ...This page is intentionally left blank...