Check that

the control unit is connected as per instructions on page 10.
Connection voltage 230-240 V +/-15%, 50/60 Hz.

Check that

the motor is wired for 3 x 230 V. If there is an operating switch between 
the motor and the control unit, the motor thermal contact should be  
connected via the auxiliary terminal in the operating switch.

Check that

the input signal is 0-10 V

.

Check that

the cleaning function and rotation monitor DIP switch are set to ON.

Check that

the frequency DIP switch is set to 100 Hz for normal wheel speed  
(10-12 rpm).

PUTTING THE EQUIPMENT INTO OPERATION

 

Should be done in sequence. 

Check that

the motor rotates in the right direction in relation to the wheel's direction 
of rotation. In the event of a fault, switch two phases to the motor.

Adjustment of max. 
speed

Set the High Speed DIP switch to the ON position. 
Adjust "Max. speed" so that the wheel rotates at 10-12 rpm  
(or as per directions from wheel manufacturer).
After a test run, set the DIP switch to OFF.

Checking minimum 
speed

Set the Low Speed DIP switch to ON. 
Check that the wheel starts. 
The minimum speed is preset. 
After a test run, set the DIP switch to OFF.

Checking the cleaning 
function

Switch off the voltage.
Make sure the “Cleaning” DIP switch is set to ON and the input signal is 
disconnected. When power is switched on, the wheel will rotate at  
minimum rpm for 10 seconds.

Checking the rotation 
monitor

The yellow Rotation LED will flash when the magnet passes the magnetic 
sensor, regardless of DIP switch position.

Finish by

having the control unit drive the wheel at maximum and minimum  
rotation speed and checking that the wheel speed is correct. 

CHECKS BEFORE POWERING UP THE CONTROL UNIT   

11

Содержание MicroMax750

Страница 1: ...IBCcontrol Made in Sweden MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MicroMax750 Article no F21075401...

Страница 2: ......

Страница 3: ...5 Technical data 6 Functions 6 DIP switch 7 Operational indications 7 Alarms 8 9 Settings via potentiometer 9 Push button 9 Connection diagram 10 Connections 10 Checks before powering up the control u...

Страница 4: ...t Disposal and recycling When replacing components or when the control unit in its entirety need replacing please follow the advice below The aim should always be maximum possible recycling of raw mat...

Страница 5: ...in power before removing the cover Never touch electrical components or contacts while main current is switched on Risk of electric shock resulting in serious injury or death Residual voltage remains...

Страница 6: ...EMC Directive 2004 108 EC All control units are approved according to the requirements of the EMC Directive 2004 108 EC and are tested according to standard EN 61800 3 2004 emission category C1 and im...

Страница 7: ...peed is necessary rotor diameter should be reduced Heat exchanger rpm and thus thermal efficiency are governed by the control unit so that wheel speed is proportional to the input signal from the cont...

Страница 8: ...ower input max 1100 W Input current max 5 0 A External fuse max 10 A Output voltage 3x0 230 V Min frequency Fixed 4 Hz Max frequency 40 100 150 Hz Motor output max 750 W Motor current 3 6 A Exact valu...

Страница 9: ...l rotates at the set maximum rpm when the switch is set to ON After a test run make sure the DIP switch is set to OFF Low speed The wheel rotates at the fixed minimum rpm when the switch is set to ON...

Страница 10: ...o normal mode when the temperature drops See Overcurrent on page 9 Overvoltage Alarms and trips if the connection voltage exceeds 276 V for more than 4 5 seconds Undervoltage Alarms and trips if the p...

Страница 11: ...after 4 5 seconds The motor is too small in relation to rotor diameter Wheel rotation sluggish Damaged motor e g bearing fault Measure amperage NOTE Precise voltages and amperages can only be obtaine...

Страница 12: ...Must be jumped if the temperature switch is not connected Alarm relay 13 14 15 Closes between 14 15 in the event of an alarm or voltage drop out Max 8 A resistive load 250 V AC Input signal 2 3 0 10...

Страница 13: ...hases to the motor Adjustment of max speed Set the High Speed DIP switch to the ON position Adjust Max speed so that the wheel rotates at 10 12 rpm or as per directions from wheel manufacturer After a...

Страница 14: ...LAND Motor cable lflex Classic 110 CY 7G0 75 Shielded Incoming EKK 3G1 5 Not shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EMC Dir...

Страница 15: ...YOUR NOTES 13...

Страница 16: ...IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Tel 46 0 42 33 00 10 Fax 46 0 42 33 03 75 www ibccontrol se info ibccontrol se IBCcontrol F21075901 Version 2 0 2015 07 01...

Отзывы: