Check that
the control unit is connected as per instructions on page 10.
Connection voltage 230-240 V +/-10%, 50 Hz.
Check that
the motor is wired for 3 x 230 V. If there is an operating switch between
the motor and the control unit, the motor thermal contact should be
connected via the auxiliary terminal in the operating switch.
Check that
the input signal is 0-10 V
.
Check that
the cleaning function and rotation monitor DIP switch are set to ON.
CHECKS BEFORE POWERING UP THE CONTROL UNIT
11
Input signal
(2-3)
0-10 V.
Plus connected to terminal 2, minus to terminal 3.
Rotation monitor
(9-10)
White cable connected to terminal 9, brown to terminal 10.
The magnet is installed with south side (S) towards the sensor.
Max. gap 15 mm.
Manual speed
(A1-A2)
Provides set max rpm when closed, regardless of input signal value.
Continued from previous page
Содержание MicroMax1500