EMC-INSTALLATION
EMC GLAND
External rotation monitor
LiYY 2×0.34
Not shielded
Connection voltage
3G1.5
Not shielded
Motor
NCY-HAR/UL/CSA 4G0,75
Shielded
Input signal
2×0.34/0.5
Does not need shielded
EMC glands must be used for shielded cables.
The above cables or equivalent must be used to comply with the EMC Directive.
NOTE!
When connecting the shielding to the EMC gland, it is important to connect as shown above.
13