11.3.2
Section 2: Encoder modes
Mode 0
concerns all connected encoder versions,
Modes 1 - 4
concern all incremental encoders,
Modes 5 and 6
concern all absolute encoders (SSI)
Depending on the encoder version that is connected, it is recommended to delete the
modes that are not currently used from the XML file.
However, mode 0 always has to remain available in both encoder versions.
11.3.2.1 Mode 0: Disabled
The 0 mode describes an encoder that is connected, but disabled. This entry should not
be changed and also not be commented out.
11.3.2.2 Mode 1: Pulse counter
Mode:
The number of the respective mode
ResetOnN:
True
– resets the counter if there is a high-level on N.
QuadratureMode:
True
– counting regulation according to the „quadrature mode“ (all four edges are
being counted)
False
– counting regulation according to the „direct mode“ (only the rising edge of
A is being counted).
UseFalling/RisingEdgeA/B:
True
– the respective edge is being used for the counting procedure.
For the „quadrature mode“, all four edges have to be enabled.
For the „Direct Mode“, only „UseRisingEdgeA“ is enabled
(optionally,
see chapter “B as qualifier”)