Manual
ibaMS16xDI-24V/-220V
30
Issue 1.4
10.2 Digital inputs
Digital inputs
Number
16
Design
Galvanically isolated, protected against reverse polarity,
single ended
ibaMS16xDI-24V
ibaMS16xDI-220V
Input signal
24 V DC
220 V DC
Max. input voltage
±60 V permanent
±300 V for 1 minute
Signal level log. 0
Signal level log. 1
Hysteresis
> -6 V; < +6 V
< -10 V; > +10 V
none
> -56 V; < +56 V
< -76 V; > +76 V
2
none
Input current
1 mA, constant
Debounce filter
Optional: 4 different operating modes
Sampling rate
Up to 40 kHz, freely adjustable
Frequency range
0 Hz to 20 kHz
Delay
Typ. 10 µs
Electrical isolation
Channel - channel
Channel - housing/power supply
AC 2.5 kV
AC 2.5 kV
Connector type
2 x 16-pin multi-pin;
connector, clamp-type terminal (0.2 mm
2
to 2.5 mm
2
), screw
connection, included in delivery
2
Hardware version A5 or higher
Supplier's Declaration of Conformity
47 CFR § 2.1077 Compliance Information
Unique Identifier
:
10.124200
ibaMS16xDI-220V
10.124201
ibaMS16xDI-24V
Responsible Party - U.S. Contact Information
iba America, LLC
370 Winkler Drive, Suite C
Alpharetta, Georgia
30004
(770) 886-2318-102
FCC Compliance Statement
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.