background image

 

ibaMS16xDI-24V/-220V 

Input module for digital signals 

 

Manual 

Issue 1.4 

Содержание ibaMS16-DI-24V Series

Страница 1: ...ibaMS16xDI 24V 220V Input module for digital signals Manual Issue 1 4...

Страница 2: ...registered trademark of the Microsoft Corporation Other product and company names mentioned in this manual can be labels or registered trademarks of the corresponding owners Certification The product...

Страница 3: ...ecting 11 6 3 Dismounting 11 7 Device description 12 7 1 Views 12 7 2 Indicator elements 13 7 2 1 Operating status 13 7 2 2 Status of digital inputs 13 7 3 Digital inputs X5 X6 14 7 3 1 Connection dia...

Страница 4: ...4 Issue 1 4 9 2 Configuration in ibaLogic V5 25 9 2 1 Configuring signals 25 9 2 2 Configuring the debounce filter 27 10 Technical Data 29 10 1 Main data 29 10 2 Digital inputs 30 10 3 Dimensions 31...

Страница 5: ...iba Software Manuals The documentation of the iba modular system comprises the following manuals Central units The manuals of the ibaPADU S IT 2x16 central units and ibaPADU S CM contain the following...

Страница 6: ...ossible consequences and risks on the basis of his her specialist training knowledge and experience and knowledge of the standard regulations 1 2 Notations In this manual the following notations are u...

Страница 7: ...rocess and the system or machine to be controlled there is a risk of death or severe injury The non observance of this safety information may result in a potential risk of death or severe injury The n...

Страница 8: ...s backplane not only the CPU but also up to 4 input output modules The power supply of the I O modules is provided by the backplane bus The modules offer 16 digital inputs In brief I O module for the...

Страница 9: ...pturing of measuring data Automation of industrial plants Applications with iba products ibaPDA ibaLogic etc The device is only to be applied as shown in the Technical Data 4 2 Special safety instruct...

Страница 10: ...ibaPADU S CM version 02 10 001 or later Backplane unit e g ibaPADU B4S 5 2 Software ibaPDA version 6 34 0 or later ibaLogic V5 version 5 0 2 or later Note The use of ibaLogic V5 requires the central u...

Страница 11: ...the protective ground grounding shield Connect the grounding screw on the bottom side of the housing with the protective ground grounding shield Important note Always screw tight the device and the mo...

Страница 12: ...4 5 Fixing screws Operating status indicators L1 to L4 Status LEDs L10 to L25 of the digital inputs 00 to 15 Connector X5 for digital inputs 00 to 07 Connector X6 for digital inputs 08 to 15 Figure 1...

Страница 13: ...cription L1 green Flashing On Off Device is working Device is not working switched off L2 yellow On Access to the backplane bus L3 white L4 red Off Flashing Normal status no faults Device failure Impo...

Страница 14: ...Here you can connect 16 input signals 0 15 each bipolar and electrically isolated Each channel is connected by means of two wire connection Due to the reverse polarity protection the measuring signal...

Страница 15: ...Digital input 10 L20 6 Digital input 02 6 Digital input 10 7 Digital input 03 L13 7 Digital input 11 L21 8 Digital input 03 8 Digital input 11 9 Digital input 04 L14 9 Digital input 12 L22 10 Digital...

Страница 16: ...value between 1 s 65535 s Off The measured input signal is transferred without filtering Stretch rising edge With the first rising edge the input signal red switches to logical 1 and keeps this value...

Страница 17: ...aits for the next edge be it rising or falling Figure 6 Debounce filter Stretch both edges Delay both edges Beginning with the first edge the output signal purple blocks the input and keeps the logica...

Страница 18: ...ules developed up to the date of release of this firmware and the corresponding software versions If a module cannot be detected yet i e it is more recent than the firmware version of the CPU this mod...

Страница 19: ...ate Figure 8 Update via Web interface 8 3 2 Update via ibaPDA Open the ibaPDA I O Manager and choose your iba modular system in the tree structure On the Diagnostics tab click on the Write firmware bu...

Страница 20: ...lso the figure above 8 4 2 Webinterface On the module Website general information about the module is only displayed You cannot change the values Important note The Web interface is only available wit...

Страница 21: ...ibaMS16xDI 24V 220V Manual Issue 1 4 21 Figure 11 notes tab...

Страница 22: ...ic detection of the module Note The automatic detection requires a bidirectional FO connection from the ibaPDA computer to the central unit Other documentation If you want to install the iba modular s...

Страница 23: ...6 e g ibaLogic then ibaPDA cannot modify the configuration of the modules and signals In this case the configuration is set by the embedded application The following entries can be displayed ibaPDA Wh...

Страница 24: ...onal comments click on the icon in the Name field Debounce filter In the dropdown menu you can choose the operating mode for the debounce filter You have got the following settings at your disposal Of...

Страница 25: ...tions You find the basic way of proceeding description in the separate ibaPADU S IT 2x16 manual This manual describes only the signals belonging to this module 9 2 1 Configuring signals The signals ca...

Страница 26: ...d as output or input resources Signal Description Inputs DI_24V_Ch 00 15 Digital input signals StatusIn Status information about the plugged input module for output module without function 0 Module no...

Страница 27: ...als DebounceTimeUsx debounce time for the single digital signal First drag the output signals defined in the I O configurator to the margin of the programming surface in this example X1_DebType_Ch00 a...

Страница 28: ...amming surface Create a new OTC assign a meaningful name e g debounce time and choose Input as type Enter the debounce time in s in the Default value field The value can be 65535 at max Now connect th...

Страница 29: ...n Storage transport 2 F to 122 F 0 C to 50 C 13 F to 158 F 25 C to 70 C Installation position Vertical plugged into backplane bus Installation height Up to 6562 ft 2000 m Cooling Passive Humidity clas...

Страница 30: ...hannel housing power supply AC 2 5 kV AC 2 5 kV Connector type 2 x 16 pin multi pin connector clamp type terminal 0 2 mm2 to 2 5 mm2 screw connection included in delivery 2 Hardware version A5 or high...

Страница 31: ...ibaMS16xDI 24V 220V Manual Issue 1 4 31 10 3 Dimensions Figure 20 Module dimensions ibaMS16xDI 24V dimensions in mm Figure 21 Module dimensions ibaMS16xDI 220V with groundig screw dimensions in mm...

Страница 32: ...he product Contact Headquarters iba AG Koenigswarterstrasse 44 D 90762 Fuerth Germany Phone 49 911 97282 0 Fax 49 911 97282 33 E mail iba iba ag com Mailing address iba AG Postbox 1828 D 90708 Fuerth...