Starting Procedures 

When using this product for the first time, pursue work while making sure to avoid omission and incorrect 
wiring by referring to the procedure below. “PC” stated in this section means “PC software”. 
This section explains the procedure for starting up the Gateway Unit. For the settings and wiring of each of 
the individual devices, controllers, and actuators connected to the network, refer to the individual device's 
Instruction Manual. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Troubleshooting 

On Gateway Unit, there are the monitor LEDs for the field network and SIO communication. 
You can confirm the communication establishment and also communication errors on these LEDs. 

1. DeviceNet (RCM-GW-DV) 

Gateway Unit Status Display LEDs 

LED

Color Indication

Description 

Illuminating CPU is in process. 

RUN

GN

OFF 

The power is OFF or CPU is not working. Please contact us if 
the LED does not turn ON even after the power is turned ON. 

Illuminating CPU error. Please contact us. 

G.ER

RD

OFF 

CPU is operating in normal condition. 

Illuminating

Either an error is occurred on DeviceNet module or the 
connection with DeviceNet is not established. 
Check the communication status LEDs for the connection to 
DeviceNet, and check the settings and wirings. Even if this LED 
is ON, the connection to the teaching tool is available as long as 
RUN is turned ON. 

Flashing

The port switch is ON. The interval for the flashing should be 
1sec. 

C.ER

RD

OFF 

Status is in normal condition. 

Illuminating

There is a communication 
error occurred to all the 
axes that are in SIO 
communication with the 
connected IAI controller. 

Flashing

There is a communication 
error occurred to one or 
more of the axes that are 
in SIO communication 
with the connected IAI 
controller. 

•  Check the settings in the 

parameters (No. 16 and 17) for 
each axis controller. 

•  Check the axis number settings.
•  Check the wiring connections of 

SIO communication lines. 

•  Check the terminal resistance 

devices. 

•  Check the noise prevention 

equipment. 

T.ER

RD

OFF 

Status is in normal condition. 

DeviceNet status indicator LEDs (MS: Node condition, NS: Network condition) 

LED

Color Indication

Description 

Illuminating The machine is in the normal operation. 

GN

Flashing

Connection to the master is not established. 
Check if it has been registered in the master’s scanning list. 

Illuminating

A hardware error occurred. 
Board must be replaced. Please contact us. 

RD

Flashing

There is an error occurred but it is not critical such like a 
configuration error or incorrect switch settings. 
It can be recovered with a rebuild of the settings. 

MS

− 

OFF 

Power is not supplied. 

Illuminating

The connection has been established and the communication is 
being performed normally. 

GN

Flashing

Online but network connection is not yet established. 
Communication Stop (Network is normal). Check the scan list. 

Illuminating

A communication error has 
occurred. The communication 
cannot be established due to a 
duplication of node addresses or a 
Busoff (communication stop due to 
frequent data error detection). 

RD

Flashing

A communication error has 
occurred. 
(Communication time-out is detected.)

Check the node address 
settings, baud rate 
setting, communication 
line wiring connections, 
terminal resistance 
connections, 
communication power 
supply, noise prevention, 
etc. 

NS

OFF

 

The machine is not on-line. The power to the DeviceNet is not 
supplied. 

Refer to Instruction Manual for the details of the DeviceNet status check. 

SIO Communication Status Display LEDs 

LED

Color Indication

Description 

Flashing

Data is being sent (from Gateway Unit to IAI controller). 

TxD

GN

OFF 

Data sending is being stopped (from Gateway Unit to IAI 
controller). 

Flashing

Data is being received (from IAI controller to Gateway Unit). 

RxD

GN

OFF 

Data receiving is being stopped (from IAI controller to Gateway 
Unit). 

 
 
 
 
 
 

2. CC-Link (RCM-GW-CC) 

Gateway Unit Status Display LEDs 

LED Color Indication 

Description 

Illuminating  CPU is in process. 

RUN 

GN 

OFF 

The power is OFF or CPU is not working. Please contact us if 
the LED does not turn ON even after the power is turned ON. 

Illuminating  CPU error. Please contact us. 

G.ER RD 

OFF 

CPU is operating in normal condition. 

Illuminating 

Either an error is occurred on CC-Link module or the connection 
with CC-Link is not established. 
Check the communication status LEDs for the connection to 
CC-Link, and check the settings and wirings. Even if this LED is 
ON, the connection to the teaching tool is available as long as 
RUN is turned ON. 

Flashing 

The port switch is ON. The interval for the flashing should be 
1sec. 

C.ER RD 

OFF 

Status is in normal condition. 

Illuminating 

There is a communication 
error occurred to all the 
axes that are in SIO 
communication with the 
connected IAI controller.

Flashing 

There is a communication 
error occurred to one or 
more of the axes that are 
in SIO communication 
with the connected IAI 
controller. 

•  Check the settings in the 

parameters (No. 16 and 17) for 
each axis controller. 

•  Check the axis number settings. 
•  Check the wiring connections of 

SIO communication lines. 

•  Check the terminal resistance 

devices. 

•  Check the noise prevention 

equipment. 

T.ER 

RD 

OFF 

Status is in normal condition. 

CC-Link status indicator LEDs (MS: Node condition, NS: Network condition)

 

LED Color Indication 

Description 

Illuminating 

The machine is in the normal operation. (Illuminated once 
communication started) 

RUN GN 

OFF 

Not in the network or timeout (The illumination is turned off if the 
communication is shut off for a certain time.) 

Illuminating  Baud rate or station number setting is not correct. 

Flashing 

Error in reception data to self station. (CRC error : Data error is 
detected) 

ERR RD 

OFF 

Status is in normal condition. 

Illuminating  Data is being received. 

RD GN 

OFF 

There is no received data. 

Flashing  Data is being sent. 

SD GN 

OFF

 

There is no sent data. 

Refer to Instruction Manual for the details of the CC-Link status check. 

SIO Communication Status Display LEDs 

LED Color Indication 

Description 

Flashing  Data is being sent (from Gateway Unit to IAI controller). 

TxD GN 

OFF 

Data sending is being stopped (from Gateway Unit to IAI 
controller). 

Flashing  Data is being received (from IAI controller to Gateway Unit). 

RxD GN 

OFF 

Data receiving is being stopped (from IAI controller to Gateway 
Unit). 

 
 
 

  

No→

Yes 

→ 

←Yes

 

←Yes

→No

Check of Packed Items
Has everything been received?

Contact us or our distributor.

Installation and Wiring
Following Instruction Manual and this guide, set Gateway Unit 
and have the wirings for the network and SIO completed.
Also, have all the wirings done for the power supply, actuator 
motor and encoder cable following the instructions on the 
Instruction Manual for each controller.

Point Check Item
• Is frame ground (FG) connected?
• Has the noise countermeasure been taken?
• Is the terminal treatment conducted on the shielded wire?
• Is the terminal resistance connected?

Initial Settings of Gateway Unit
Ensure the settings for the mode, field network baud rate and 
node addresses (station numbers) comply with the system.

Initial Settings of IAI Controller Connected to Gateway Unit
• Have the settings for axis numbers.
• Have the setting for Parameter No. 16 SIO Baud Rate to 230.4kbps.
• Have the setting for Parameter No. 17 Slave Station Transmitter Activation Minimum Waiting Time to 2msec.
• Have all other necessary parameter settings done. 

PLC (Master Unit) Baud Rate
Have the settings for the node addresses (station numbers) 
and baud rate. 

Important Check Item
Is the programmed Gateway control sequence 
complied with the operation mode and the system?

Power Supply
1) Supply the power to the IAI controller that is connected to Gateway Unit.
2) Supply the power to Gateway Unit
3) Supply the power to PLC (master unit)
  

Communication Establishment Check
• Confirm that the communication has been established by checking 
the monitor LEDs on Gateway Unit.
[Refer to Troubleshooting Section.]
• Are the LEDs turned on in normal condition? Is PLC (master unit) 
  side also in normal condition?
(Note) Refer to the PLC and master unit instruction manuals for the 
           details how to check on the master unit side.

Reconfirm all the settings following the procedure 
in this chart while referring to the Instruction Manual 
for each unit, controller and PLC.

Communication is established. Move on to the system operation check and adjustment.

↓ Yes

↓ 

Содержание RCM-GW

Страница 1: ...ication Communication Protocol RS485 conformance Communication System Start Stop Synchronization System Half Duplex Communication Baud Rate 230 4kbps Error Control System Non parity bit CRC 1 Communication Cable Length Total Cable Length 100m or less Communications Cable Twisted pair shielded cable Recommended Taiyo Cabletec Corporation K SB 20276 Length m 2P AWG22 Environment Surrounding air temp...

Страница 2: ...Enable Always ON b contact Enable SIO Communication Line Wiring Layout There should be no problem to have a terminal block connection instead of a 4 way junction Use a terminal block connection or direct joint connection if there is a concern that a faulty connection may occur as a result of using the E Con connector 17 5 17 5 φ5 Hole 178 5 170 5 161 68 1 RCM GW DV RCM GW CC RCM GW PR Note Dimensi...

Страница 3: ...and the extended cyclic settings cannot be used for other purposes Refer to Instruction Manual DVD for the details of the address assignment No Mode Remote I O Data Register GW PLC RX PLC RY GW GW PLC RWr PLC RWw GW 1 Position number specification mode 7 words 7 words 9 words 9 words 2 Direct numeric specification mode Position Data Limit Mode 7 words 7 words 16 words 16 words 3 Normal Positioning...

Страница 4: ...d ON Illuminating CPU error Please contact us G ER RD OFF CPU is operating in normal condition Illuminating Either an error is occurred on CC Link module or the connection with CC Link is not established Check the communication status LEDs for the connection to CC Link and check the settings and wirings Even if this LED is ON the connection to the teaching tool is available as long as RUN is turne...

Страница 5: ...ating Status is off line OFF The machine is not off line ERR RD 1Hz Flashing There is a configuration error Exnample The number of input and output set with the mode setting switch does not match with the number of input and output set with the configuration tool 4Hz Flashing It is a communication board ASIC initializing error Please contact us if the condition does not recover even with a reboot ...

Отзывы: