Hyundai HACM09DB - HCCM99DB Скачать руководство пользователя страница 13

ECR International

Hyundai Ductless Split System

13

1. Cutting and flaring of

tubing:

A.

 Cut the tubing on its

straight part with the
pipe cutter.

B.

 Remove burrs from cut

edges of pipes, which
may cause a gas leak.

C.

 Flaring of the pipe is

done with the flaring
tool.

NOTE:

 

Do not forget to in-

stall the flare nut before
flaring

2. Pre-Connecting:

Screw the tubing turning
3 to 5 times until hand

tight.

3. Fastening:

 Fasten the connection.

• Apply refrigeration oil to

the flare surface to pre-
vent gas leakage.

     Leak Test

 Leak Check

Check the joints with a gas
leak detector or soapy water for
refrigerant leaks. If a leak is
found, repair and recheck.

     Drainage

Indoor Unit

After the indoor unit(s) have been installed, make sure that
condensed water is properly drained.  (If this is neglected,
the unit(s) may become flooded.)

Special care should be given to the following details:

Outdoor Unit (Heat Pump Only)

NOTE:  Allow clearance for drainage of water or condensate.

For outdoor condensation:

• The outdoor unit has drain outlets on the base to drain

condensation to the outside.

• To drain condensation by hose (5/8” hose) with the drain

socket, connect the socket to the center of the base and
cover all other outlets with base caps.

• Install the outdoor unit on a flat level surface and make

sure condensation drains smoothly.

• In cold areas, condensation

and defrost water can freeze,
therefore do not use the drain
outlet caps during the cold sea-
son.

• Electrical connection should

only be made by a qualified pro-
fessional.

• See the “Determination of Installing Position”.

Connecting of Tubing

INSTALLING OF THE OUTDOOR UNIT

1) Remove the cap from the service port on the suction line service

valve.

2) Connect the suction side of the refrigerant gauge manifold to

the Suction Line service valve.  Connect the center hose of the
refrigerant manifold gauge to the micron gauge.  Connect the
other side of the micron gauge to the vacuum pump.  (Diagram 1)

3) Open the suction side of the refrigerant manifold set and turn

the vacuum pump on.  

NOTE:  Evacuate the system down to

400 microns.

4) When the system pulls down to 400 microns turn the vacuum

pump off.  Observe the micron gauge: if the system has a leak
the gauge will detect it.  If there is a leak, find it, repair it, and
repeat steps 3 and 4.

5) Close the refrigerant gauge manifold valve and disconnect the

vacuum pump from the system.

6) Remove the Suction and Liquid line Service Valve Caps from the

valves.

7) Using an Allen wrench, open the Liquid Line Service Valve until

the valve is in the fully open position.  Next do the same for the
Suction Line Service valve. 

NOTE: Be careful as not to

completely remove the valve core from the valve.  This
will result in the release of refrigerant from the system
into the atmosphere!

8) Re-install the caps on both service valves.  This completes the

charging of the system.

!  

CAUTION  

 !

Cut pipe by rotating the

pipe cutter

Pipe

Turn the handle
Clockwise while
pushing it against
the pipe

Pipe cutter
knife

Yoke

Do not dam-
age the in-
side of the
pipe.

Bar

Flare nut

Fix pipe
turning clamp
handle.

Pipe

• Drain hose must

slope downward
to the outdoor
side.

• Do not use a trap

or kink.

• Never put the

end of the drain
hose into the
water.

• Do not tilt up-

ward.

Flare nut

Flare valve

Manifold gauges

Charge

cylinder

Discharge

Suction

Vacuum pump

INDOOR

UNIT

O

U

T

DOOR

UNIT

Diagram 1

Air Purge and Charging

(SINGLE ZONE SYSTEM SHOWN)

Содержание HACM09DB - HCCM99DB

Страница 1: ...GONLY HACW09DB HCCW09DB HACW12DB HCCW12DB HACW18DB HCCW18DB HACW24DB HCCW24DB COOLINGANDHEATING HAHW12DB HCHW12DB HAHW18DB HCHW18DB HAHW24DB HCHW24DB MULTI ZONE COOLINGONLY HACM09DB HCCM99DB HACM12DB HCCM22DB COOLINGANDHEATING HAHM09DB HCHM99DB HAHM12DB HCHM22DB ECR INTERNATIONAL 85 Middle Rd Dunkirk NY 14048 Ph 716 366 5500 Fax 716 366 1209 www ecrinternational com ...

Страница 2: ... not modify the system s It may increase the risk of fire SAFETY TIPS FOR OPERATION CAUTION MELODY BUZZER When selecting ON OFF and function changes a melody will sound from the indoor unit s to indicate that the change has occurred DEODORIZING FUNCTION In case of DRY and COOL mode the fan or indoor unit s will not turn ON for 40 seconds even after starting the operation in order to deodorize vari...

Страница 3: ...he season set the Hand Switch Lever to ON I position After the season set the Hand Switch Lever to OFF O position Hand Switch Lever The Remote Control is stored inside the product Please open the front grill to remove the Remote Remote Control Storage Air Intake Left side Rear Drain Hose Air Outlet Interconnection cable pipes and power supply Air Outlet Drain Hose Air Intake Left side Rear Interco...

Страница 4: ...t let children play with the Remote Control To avoid interference the indoor unit and the Remote control unit should be at least 3 feet away from a TV set or a radio In cases where than two air conditioners are installed in the same room individual operation may not be possible Transmitter Low Battery Indicator Display Window ON OFF Button Temperature Setting Button High Power Button One Hour Time...

Страница 5: ...ou wish 1 Press the MODE button on the Remote Control Cold weather High humidity Hot weather When air circulation is needed HEAT mode DRY mode COOL mode CIRCULATE mode 2 Press the ON OFF button When the fan speed or air flow direction is to be changed When the set temperature is to be changed Room Temperature Over 27 C 81 F 20 27 C 68 81 F Below 20 C 68 F Operating Mode Cool Dry Heat Set Temp Moni...

Страница 6: ...contaminating status of air filter In this case please clean or replace the air filter with a new one OPERATION Continued FAN SPEED AIR FLOW DIRECTION To operate the unit s effectively it is recommended that you familiarize yourself with the following functions To change the fan speed Press the FAN SPEED button Cold air moves down horizontal air flow is preferred when cooling To change the air flo...

Страница 7: ...HIGH POWER mode button is pressed heated or cooled air comes into the room at a higher fan speed for 15 minutes The fan speed changes rhythmically between high and ultra high When the air conditioner s continue to run on HIGH POWER mode in a large room they may not reach the set room temperature due to limited cooling capacity This may cause water drops to form around the outlet In such cases plea...

Страница 8: ...g the 1HR TIMER button again during the ONE HOUR TIMER mode the unit will stop operation ap proximately one 1 hour later The ONE HOUR TIMER mode has preference over other Timer modes If pressing the 1HR TIMER button again during the OFF TIMER mode the unit s will stop operat ing approximately one 1 hour later EMERGENCY OPERATION When the remote control cannot be used due to dead batteries or out o...

Страница 9: ...nd cleaning powder may damage the coated surface or the plastics Do not use water higher than 40 C 104 F or the air filters may shrink and the plastic materials may be dam aged Do not touch the evaporator coil when removing and re placing the air filters Injury may occur Never operate the unit without the air filters 1 CLEANING AIR FILTERS ONCE EVERY TWO WEEKS Clean the air filters at least once e...

Страница 10: ...put the switch lever s on the indoor unit s in off O position 18 24 Btuh Blinking Green LED Red LED Green LED Defect of indoor heat exchanger sensor Defect of compressor protection circuit Cooling only Model Trouble Check by Self Test Mode Contents of Defect Defect of room temperature sensor PLEASE CHECK THE FOLLOWING THE UNIT S WON T OPERATE Check the batteries in the Remote Control Check that th...

Страница 11: ...n 18 24 Btuh Rubber Cushion 3 Drain Pipe 1 1 2 Parts of Indoor Unit Parts of Outdoor Unit 4 4 Be sure chosen location can properly support the weight of the unit s and will provide adequate damping of vibration and noise Outdoor Unit Insure chosen location can provide adequate drainage and good ventilation Do not install in an area with flammable or corrosive vapors Avoid salty air or sulfuric gas...

Страница 12: ...stallation plate horizontally and securely on structural members studs etc in the wall with four 4 installing screws See Fig 1 3 Make a 2 9 16 hole through the wall Hole should be angled down to the exterior See Fig 2 4 Use a city grade wall pipe outer diameter 2 3 8 as a sleeve to protect the interconnection cable and the pip ing See Fig 2 When inserting the pipes protect the ends from dust or mo...

Страница 13: ... OUTDOOR UNIT 1 Remove the cap from the service port on the suction line service valve 2 Connect the suction side of the refrigerant gauge manifold to the Suction Line service valve Connect the center hose of the refrigerant manifold gauge to the micron gauge Connect the other side of the micron gauge to the vacuum pump Diagram 1 3 Open the suction side of the refrigerant manifold set and turn the...

Страница 14: ...ated voltage marked on the indoor unit label s Connect one end of the ground wire to the outdoor unit ground terminal Use minimum 14 AWG wire conductors between the in door and outdoor units Refer to page 16 to determine the wire size from the power supply to the condenser CAUTION Make sure wire connections are secure otherwise elec trical malfunction may occur Cool and Heat Model HYUNDAI ELECTRIC...

Страница 15: ...h Single or Multi Zone Be sure to check the power source then turn the power on Check the installation again First set the lever to OFF O position then to ON I and TEST position slowly During the test the indicator light will blink 18 24 Btuh 9 12 Btuh 1 Wiring between units should be cut to length 2 Remove the wiring cover of the Indoor Unit s and the Outdoor Unit 3 Insert the connection wire int...

Страница 16: ...ealant to prevent rain or wind When using the pipe cover fill the gap in the wall through hole in the inside Nominal 5 Sensible AMPS HP RLA LRA AMPS HP HMCW18000 1 18 000 12 600 10 9 208 230 60 1 0 72 0 2 4 45 26 0 22 0 06 10 1 11 1 15 197 HMHW18000 2 17 400 11 700 10 0 17 700 6 8 208 230 60 1 0 72 0 2 4 45 26 0 22 0 06 10 1 11 1 15 197 HMCW24000 3 24 000 15 500 10 6 208 230 60 1 0 72 0 2 5 85 29 ...

Страница 17: ... 5 75 Room Temp F 5 0 4 5 59 68 77 86 95 104 Outdoor Intake Temp F Running Current A Outdoor Fan Speed Low Pressure PSI Outdoor Fan Speed Room Temp F Low High Low High 99 85 86 80 71 75 57 43 59 68 77 86 95 104 Outdoor Intake Temp F 12 86 10 80 75 8 Room Temp F 6 59 68 77 86 95 104 Outdoor Intake Temp F Running Current A Outdoor Fan Speed Low Pressure PSI Outdoor Fan Speed Room Temp F Low High Low...

Страница 18: ...ECR International Hyundai Ductless Split System 18 OPERATING CHARACTERISTICS Single Zone Heating All units operating on high speed fan HHW12000 HHW18000 HHW24000 ...

Страница 19: ... 75 57 43 59 68 77 86 95 104 Outdoor Intake Temp F 5 86 4 5 80 75 4 Room Temp F 3 5 59 68 77 86 95 104 Outdoor Intake Temp F Running Current A Low Pressure PSI Room Temp F 99 85 86 71 80 75 57 43 59 68 77 86 95 104 Outdoor Intake Temp F 8 7 Room Temp F 86 6 80 75 5 4 68 77 86 95 104 Outdoor Intake Temp F Running Current A Low Pressure PSI Room Temp F THERMISTER CHARACTER DIAGRAMS ...

Страница 20: ......

Отзывы: