![Hytronik SensorDIM HEC7030 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/hytronik/sensordim-hec7030/sensordim-hec7030_manual_2194945006.webp)
Stand-by dimming level
Stand-by period (corridor function)
Press the buttons of “stand-by period” to set stand-by period at 0s / 10s / 1min / 10min / 30min / +∞.
* “0s” means on/off control; “+∞” means bi-level dimming control, light never switches off when daylight sensor is disabled.
Press the buttons of “stand-by dimming level” to set the stand-by dimming level at 10% / 20% / 30%.
Detection Pattern
W
all mounting height (m)
Ceiling mounted detection pattern (m)
Wall mounted detection pattern (m)
Ceiling mounted height (m)
4
9
0
5
4
0
10%
10%
30%
30%
75%
75%
50%
50%
I – 100%
II – 75%
III – 50%
IV – Sensor OFF
100%
75%
50%
Sensor OFF
DIP Switch Settings
1
Detection Range
Sensor sensitivity can be adjusted by selecting the combination on the DIP
switches to fit precisely for each specific application.
1 2
Note: by choosing “Sensor OFF”, it becomes an ordinary driver without
occupancy detection.
I – 5s
II – 30s
III – 3min
IV – 10min
2
Hold Time
Select the DIP switch configuration for the light on-time after presence detection.
This function is disabled when natural light is sufficient.
5s
30s
3min
10min
4
3
I
II
III
IV
Note: this function is disabled when the natural daylight exceeds the daylight threshold
setting for more than 5minutes.
I – Disable
II – 50Lux
III – 10Lux
IV – 5Lux
Disable
50Lux
10Lux
5Lux
5 6
3
Daylight Threshold
Set the level according to the fixture and environment. The light will not turn on if
ambient lux level exceeds the daylight threshold preset.
Please note that the ambient lux level refers to internal light reaching the sensor.
Disabling the daylight sensor will put the sensor into occupancy detection only mode.
Subject to change without notice.
Edition: 26 Feb. 2020 Ver. A0 Page 6/8