![Hytronik HMW30 Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/hytronik/hmw30/hmw30_manual_2194932003.webp)
zero-cross point
Alternating current
Zero-cross Relay Operation
Designed in the software, sensor switches on/off the
load right at the zero-cross point, to ensure that the
in-rush current is minimised, enabling the maximum
lifetime of the relay.
3
A rotary switch is built inside the sensor for scene
selection / fast programming. Total 16 channels
are available:
Rotary switch preset
Rotary Switch Preset
Note: settings can also be changed by remote control
HRC-11. The last action controls.
0
5s
100%
Disable
1
1min
100%
2Lux
2
5min
100%
10Lux
3
5min
100%
30Lux
4
5min
100%
10Lux
5
5min
100%
30Lux
6
5min
100%
Disable
7
10min
100%
2Lux
8
10min
100%
10Lux
9
10min
100%
30Lux
A
10min
100%
Disable
B
10min
75%
30Lux
C
10min
50%
10Lux
D
30min
100%
50Lux
E
30min
100%
Disable
F
5s
100%
2Lux
Detection
range
Channel
Hold-time
Daylight
sensor
Wiring Diagram
Detection Pattern
Ceiling mounted height(m)
10
0
20
10%
30%
75%
50%
HMW30
Brown
LED driver
L
N
L
N
Blue
Grey
www.hytronik.com
On/off Control
2
This sensor is a motion switch, which turns on the light upon detection of motion, and turns off after a pre-selected hold-time when
there is no movement. A daylight sensor is also built in to prevent the light from switching on when there is sufficient natural light.
* For single person walking across, the detection range is reduced by 1/3.
(forklift)