It’s commonly known Microwave and Infrared are main detecting technologies in lighting controls. Both have the advantage and 
disadvantage for industrial applications.

The remedy is to create Dual Sense by combining both technologies to make use of the advantage and bypass the disadvantage.

* sensitive to minor motion. 
* sensitive to radial movement.
* can be reflected by objects hence covering big detection area
* resilient to heat source, smoke and and air conditioner.

* penetrates walls, picks up motions outside of the office area; 
* back wave detection, false trigger by motions at the back.
* can be false triggered by ventilation fans, water pipe, elevators 
   etc. in industrial application.

* no penetration, confined detection area. 
* sensitive to tangential movement. 
* resilient to motion object which has no heat radiation.

* can be false triggered by air conditioner, smoke and 
   other heat sources.

Dual Sense Introduction

HF

PIR

Advantage

Disadvantage

Disadvantage

Advantage

* HF: Microwave only
* PIR: PIR mode only
* HF+PIR: both PIR and microwave mode, to decrease the detection capability and detection area. Only when both detections are 
                activated, the motion is considered valid. This is to prevent the sensor from false trigger by heat source, air conditioner, 
                ventilation fans, water pipe and elevators etc...
* HF/PIR: either PIR or microwave mode, to increase the detection capability and detection area;

4 optional detection modes via remote control: 

Sensor

Sensor

min 6m

Distance Recommended between Sensors

Pay attention: The RF signal could be affected by big metal 
plate & wireless devices such as GSM mobile antenna, strong 
Wifi signal, ultra high-voltage cable which emits frequent 
electromagnetic waves radiation, which may interfere with the 
RF transmission and communication! Please always check the 
application environment before mass installation!

We recommend the mounting distance between sensors to be 
more than 6m to avoid sensors from being false-triggered.

433/868

315/915

9

0

15

Detection Pattern

Ambient daylight 

threshold

One-Key
Commissioning

Photocell

Intelligent

Rotary Switch 

Grouping

Photocell Advance

TM

Functions and Features

Tri-level Control (Corridor Function)

1

Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas which require a light change notice 
before switch-off.  The sensor offers 3 levels of light: 100%-->dimmed light (natural light is insufficient) -->off; and 2 periods of 
selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.  

Содержание HIM38/RF

Страница 1: ...ve 1200W resistive max 20 devices max 40mA Capacitive Sensor RF Data Operation temperature Ta 20 O C 50 O C Environment IP65 IP rating Model No 0 2mW HF 5 8GHz 75MHz HF High Frequency microwave PIR Sensor principle Operation frequency Transmission power Detection range Detection angle RF frequency RF transmission distance Max O x H 18m x 15m 868MHz FSK mode default 30m indoor 50m outdoor 30s Warmi...

Страница 2: ...ared remote receiver 1 10V 1 10V L N N L Installation hole 71 5 4 2 37 5 38 3 25 11 8 78 2 87 1 HC034RF 1 10V output RF grouping by rotary switch or remote control C Attach to the shade by clamp B Screw to the Luminaire by conduit Cable entry Sensor module PIR LED indicator Infrared receiver Rotary switch for programing Daylight sensor 59 6 66 6 89 9 0 825 75 64 43 8 43 59 3 73 5 35 2 57 3 47 5 Se...

Страница 3: ...n is considered valid This is to prevent the sensor from false trigger by heat source air conditioner ventilation fans water pipe and elevators etc HF PIR either PIR or microwave mode to increase the detection capability and detection area 4 optional detection modes via remote control Sensor Sensor min 6m Distance Recommended between Sensors Pay attention The RF signal could be affected by big met...

Страница 4: ...at the fixture never switches off but stays at preset dimming level even when natural light is sufficient zero cross point Alternating current Zero cross Relay Operation HIM38 RF Designed in the software sensor switches on off the load right at the zero cross point to ensure that the in rush current is minimised enabling the maximum lifetime of the relay 3 RF Grouping by Rotary Switch Maximum 15 c...

Страница 5: ... Feb 2020 Ver A0 Page 5 9 Night Daytime HIM39 RF Brown LED driver L N DALI DALI L N Blue Red Black HIM38 RF Brown LED driver L N 1 10V 1 10V L N Blue Grey Red Black Wiring Diagram HC034RF LED Driver N N 1 10V N N L L L L _ 1 10V _ Wiring Diagram ...

Страница 6: ...red for selection For single person walking across the detection range is reduced by 1 3 PIR detection H x D 15 x 18m max HF detection H x D 15 x 14m max PIR HF PIR tangential movement 18m HF walking across 14m 15m PIR detection L x W x H 18 x 5 x 15m max HF detection H x D 15 x 14m max PIR HF 15m 18m 14m 5m PIR HF PIR detection L x W x H 5 x 18 x 15m max HF detection H x D 15 x 14m max 15m 5m 14m...

Страница 7: ...ight brightness during hold time Load Indication The light will flash ONCE rapidly after receiving the commamd from the remote control successfully Brightness Scene program 1 key commissioning Detection range for Transceiver only Press buttons in zone Detection range to set detection range at 100 75 50 10 Daylight threshold 1 Press button Start to program 2 Select the buttons in Detection range Da...

Страница 8: ...e refer to steps below Short press Learn Erase button on RC to activate pairing mode and the receiver unit starts to beep once every second for 3min Note up to 30 units can be paired Short press Transmit button on RC the commander unit master unit beeps one time to send the transmission signal Upon receiving the transmission signal the receiver unit slave unit rapidly beeps 3 times in 1s to indica...

Страница 9: ...Regarding precautions for PIR sensor installation and operation please kindly refer to www hytronik com download knowledge PIR Sensors Precautions for Product Installation and Operation 3 Regarding precautions for RF sensor installation and operation please kindly refer to www hytronik com download knowledge RF Sensors Precautions for Product Installation and Operation 4 Regarding Hytronik standar...