Set the level according to the fixture and environment. In Photocell Advance
TM
mode this level will determine at which point the light turns off, and automatically
turns back on again (stand-by time is set to infinity).
Please note that the levels refer to internal light reaching the sensor.
Disabling the daylight sensor will put the sensor into occupancy detection only
mode.
Select the dip switch configuration for the full brightness on-time after presense
detection.
Please note that this function is disabled when the natural daylight exceeds the
daylight threshold setting for more than 5 minutes.
1
Detection Range
2
Hold Time
3
Daylight Threshold
5
Stand-by dimming level
4
Stand-by period (corridor function)
Sensor sensitivity can be adjusted by selecting the combination on the DIP
switches to fit precisely for each specific application.
I – 100%
II – 50%
I – 0s
II – 10s
III – 1min
IV – 5min
V – 10min
VI – 30min
VII – 1h
VIII – +∞
I – Disable
II – 50Lux
III – 10Lux
IV – 2Lux
This is the time period you would like to keep at the low light output level
before it is completely switched off in the long absence of people.
I – 10%
II – 30%
I – 5s
II – 3min
III – 10min
IV – 30min
50%
100%
1
I
II
1h
10min
30min
5min
1min
10s
8
7
6
+∞
0s
I
II
III
IV
V
VI
VII
VIII
5
4
50Lux
10Lux
2Lux
Disable
I
II
III
IV
30%
10%
9
I
II
3
2
3min
10min
30min
5s
I
II
III
IV
8
DIP Switch Settings
The setting is used to select the desired dimmed light level used in
periods of absence for enhanced comfort and safety.
Note: “0s” means on/off control;
“+ ∞ ”means the stand-by time is infinite and the fixture is effectively
controlled by the daylight sensor, automatic on/off operation based
upon daylight). Selecting other time periods will disable ‘automatic
on’ operation and the photocell is used only to turn off the fixture
automatically.