Installer Supplied Parts

The Hypro High Pressure System is provided with the

major components and accessories required for installa-

tion. Due to differences in chassis and apparatus configura-

tions, the installer must provide plumbing to satisfy individ-

ual installation requirements. The following paragraphs list

the specifications for selection of these components.

Before beginning system installation, read this section thor-

oughly to make sure the proper components are selected.

For detailed system installation instructions, refer to Pages

5 and 6. 

Suction Lines

Corrosion-resistant fittings and hoses from the foam tank to

the foam concentrate inlet of the pump must be used. Use

5/16-inch minimum inside diameter hose for the foam inlet.

Corrosion-resistant fittings and hoses from the water

source to the inlet of the pump must be used. Use only 3/4-

inch minimum inside diameter hose for the water inlet. Use

components that are rated for 23 in [584.2 mm] Hg vacuum

and 50 psi [3 bar] pressure or greater for all suction line

inlets. The components used must be compatible with all

foam concentrates to be used. All fittings used must be

made of brass, 300 series stainless or other corrosion-

resistant materials.  Before selection of components, check

for compatibility with foam concentrate. The use of clear

suction hose is recommended to allow viewing of foam and

water priming operations. The pump must be positioned to

allow gravity feed from the foam tank and water source or a

net positive suction head (NPSH) is required.

Discharge Lines

Fittings and hoses from the foam solution discharge of the

pump to the foam spray nozzle must be supplied by the

installer. Hose end fittings on gun and pump are 1/2-inch

[12.7 mm] NPT. Hose lengths and sizes are shown below.

All hoses must be rated for 1800 psi [124.1 BAR] minimum

working pressure. Fittings and hoses must be compatible

with all foam concentrates to be used. Use fittings of brass,

300 series stainless or other corrosion-resistant material

that is compatible with foam concentrates to be used.

Thermal relief valve must be plumbed to discharge away

from operator.

Check Valves

Check valves have been included with the system at the

water inlet to help prevent back flow of foam concentrate or

foam solution. The system should be disconnected from

exterior water supplies when not in use. A complete system

flush should be performed before storage to prevent com-

ponent failure due to evaporation of foam and water within

the system.

Foam Concentrate Tank

A foam concentrate tank must be supplied to suit the

capacity required for the apparatus application. The tank

should meet NFPA minimum standards for the design

capacity, including filler size, venting and drain facility. A

shut-off valve is recommended to allow cleaning of the

strainer.

Electrical Requirements

Electrical wiring must be supplied to the engine starter

switch. SEE ENGINE MANUAL for detailed electrical hook

up specifications. 

CAUTION:  Always disconnect ground before electrical

arc welding on any Hypro equipment. Failure to do so

will result in a power surge through the system that

could case irreparable damage to the electronic com-

ponents.

L-1530 (5/11 Rev. B)

Содержание Turbo Stream 1508B-130EFS

Страница 1: ...he system will accurately inject foam concentrate while the system is running at recommended operating speed and pressure Foam percentage indication is instantaneously given on the foam monitoring pan...

Страница 2: ...r handling and forcing connections can damage the components which could result in other system damage Notes are used to notify of installation operation or maintenance information that is important b...

Страница 3: ...scription The following components are packaged with the Model 1508B 130EFS Hypro High Pressure System Foam Concentrate Strainer Inlet Water Strainer Pump Motor Assembly Foam Spray Gun Wand Control Pa...

Страница 4: ...itive suction head NPSH is required Discharge Lines Fittings and hoses from the foam solution discharge of the pump to the foam spray nozzle must be supplied by the installer Hose end fittings on gun...

Страница 5: ...tem should be positioned below the foam tank discharge to allow gravity feed to the pump Place the foam tank where refilling with 5 gallon 19 liter containers and other methods is suitable for the end...

Страница 6: ...posed to this pressure must be rated at or above the operating pressure of all other discharge components 1800 psi 124 1 BAR minimum Check Valves A 3 4 inch check valve is included at pump inlet A foa...

Страница 7: ...Use only quality Class A foams 7 Measure the amount of concentrate injected over time and compare to the level indicated on the display panel during this time The output of the Hypro High Pressure Sy...

Страница 8: ...cated by the recoil starter to the ON position 2 Turn the fuel cock to the ON position 3 Push the throttle lever to a slightly open position 4 Operation of the choke lever a When engine is cold i In c...

Страница 9: ...nually Drain the pump oil and refill pump gear case with SAE 30 weight non detergent oil Check for foreign materials in the drained oil water or debris Note Water quality flushing and storage techniqu...

Страница 10: ...ings 21 44 31 31 17 94 Pulse Hose Connection Foam Concentrate Inlet 3 8 18 NPT Water Inlet Port 3 4 14 NPT Solution Outlet 1 2 14 NPT 6 69 5 31 38 22 Dia 4 2 25 3 44 Dia 6 Holes 18 25 5 62 2 63 7 68 3...

Страница 11: ...11 Notes L 1530 5 11 Rev B...

Страница 12: ...any chemical ref OSHA section 1910 1200 d e f g h and hazardous chemicals must be labeled tagged before being shipped to Hypro for service or warranty consideration Hypro reserves the right to request...

Отзывы: