3-8
S
ETUP
Operator Manual
Three-Phase - CE
Conductor
Color
Ground
Green/Yellow
L3 (W)
Black
L2 (V)
Blue
L1 (U)
Brown
Note: See also
EMC
Compatibility
and
Mains
Supply on page i for further
power (supply) cable
shielding recommendations
for CE compliance.
TB1
Green/
Yellow
V
Blue
U
Brown
W
Black
(Filter Board)
Figure 3-9
Three-Phase CE Power
POWER REQUIREMENTS
Line Voltage Disconnect Box
Use a line disconnect box for each power supply. This disconnect box allows the operator to turn the
power supply off quickly in an emergency situation. The switch should be located on a wall near the
power supply, and should be easily accessible to the operator. The interrupt level of the switch must be
equal to or exceed the continuous rating of the fuses. Use slow-blow fuses according to the power
requirements listed below.
Input
Input Current
Recommended
Voltage
Phase
@ 6.6 kw Output
Slow-Blow Fuse Size
200 VAC
1
57 amps
70 amp
208 VAC
1
55 amps
70 amp
230 VAC
1
50 amps
70 amp
240 VAC
1
47 amps
60 amp
400 VAC
1
33 amps
40 amp
480 VAC
1
28 amps
35 amp
200 VAC
3
33 amps
40 amp
208 VAC
3
32 amps
40 amp
230 VAC
3
29 amps
35 amp
230 VAC (CE)
3
31 amps
40 amp
240 VAC
3
28 amps
35 amp
400 VAC
3
18 amps
25 amp
400 VAC (CE)
3
18 amps
25 amp
480 VAC
3
15 amps
20 amp
600 VAC
3
12 amps
20 amp
Содержание powermax900
Страница 1: ......
Страница 15: ...SAFETY 1 6 Hypertherm Plasma Systems 8 99 ...
Страница 21: ...SÉCURITÉ 1a 6 08 99 HYPERTHERM Systèmes plasma ...
Страница 50: ...OPERATION 4 9 Operator Manual Figure 4 8 Dragging the Torch Figure 4 7 Cutting a Circle ...
Страница 69: ...Operator Manual 5 14 MAINTENANCE PARTS ...
Страница 73: ...APPENDIX B Operator Manual ...