2 – Power Supply Setup
Extension cord recommendations
Any extension cord must have an appropriate wire size for the cord length and system voltage. Use a cord that meets
national and local codes.
For all Powermax125 configurations, the recommended gauge size for any three-phase extension cord between
3 – 45 m (10 – 150 feet) is 10 mm
2
(8 AWG).
Engine-driven generator recommendations
Generators used with the Powermax125 should satisfy the voltage requirements in the following table and in
Based on the generator rating, age, and condition, adjust the cutting current as needed.
If a fault occurs while using a generator, turning the power switch quickly to OFF and then
to ON again (sometimes called a “quick reset”) may not clear the fault. Instead, turn OFF
the power supply and wait 60 to 70 seconds before turning it ON again.
Engine drive rating
System output current
Performance (arc stretch)
40 kW
125 A
Full
30 kW
125 A
Limited
30 kW
100 A
Full
25 kW
100 A
Limited
22.5 kW
75 A
Full
20 kW
75 A
Limited
20 kW
60 A
Full
15 kW
60 A
Limited
12 kW
40 A
Full
10 kW
40 A
Limited
10 kW
30 A
Full
8 kW
30 A
Limited