background image

WARNING

!

Single-End Power Connection 

Installation/Retrofit Guide

“Single-end” Power Connection Procedure:

1.  Ensure Breaker is turned off and no Power is going to the Fixture.    2.  Remove Fluorescent Tube and Recycle. 
3.  Open/Remove Wiring Compartment Cover and Cut-off all Wires connected to the Ballast. Remove the Ballast.
4.  Connect the Wires as shown in ( Fig. 1 ) and ( Fig. 2 ).
5.  Adapt one-end Wiring method as shown in ( Fig. 3 ) before installing the HyLite LED Tube Light.
  a. Live Wire “L” and Neutral Wire “N”, should be separately connected to any one Wire of C1 or C2. 
  b.  The Wire “L” and Wire “N” can be separately connected to more than one Wire from C1 or C2.
  c.  To avoid the risk of Electric Shock, 

DO NOT

 connect Wires “L” and “N” together. 

  d. Use approved Electrical Insulating Tape or Wire Cap to ensure that all the Power Cords which were cut are well Insulated or Capped. 

    An Energized Wire is a Shock and a Fire Hazard.  
6.  Close-up the Wiring Compartment. 

7.  Insert HyLite LED Tube Light in the Lamp Holder. 

 

Note:

 Check the Tube to ensure the “Input” end is installed in the Lamp Holder with the line and neutral installed.

8.  Once Installation is complete, switch-on Power. 

For installing the tube with AC Direct Wire connection, only one end of the tube is designated 

as the input side. Ensure only this end is installed  in the Powered Lamp Holder. Do not Remove 

Cover and/or End Caps. No User-Serviceable Parts inside.

© 2016 ARVA, LLC.,  USA

www.HyLiteLEDLighting.com

Installation Method for 4 ft. (120cm) Single-end Power Connection

Single-end Power 

Wiring Connection

L

N

Input Voltage 

AC 100-277V

Luminaire with Magnetic Ballast & Starter 

(1)  Cut-off all Wires connected to 

  the Ballast & Starter.
(2)  Connect the Wiring of Input & Output 

  of the Magnetic Ballast.

C1 C2

AC 100-277V 

50/60 Hz.

C3 C4

S

HyLite LED Tube Light

(1)

(2)

(2) 

Connect

Input Wire

Fig. 1

Luminaire

Fig. 3

L

N

HyLite 

LED T

ube Light

Wiring: Connection on one-end only.

Input side is designated on the tube. 

HyLite LED Tube Light

L

N

C1

C2

Input Voltage: 

AC 100-277V, 50/60 Hz.

HyLite LED Tube Light

C1

Remove Ballast

C2

C3

C4

AC 100-277V 

50/60 Hz.

Luminaire with Electronic Ballast

Fig. 2

HyLite LED Tube Light

Retrofit Luminaire with One Tube

L

N

AC Mains

Electronic Ballast

HyLite LED Tube

Electronic Ballast

Fluorescent Tube

AC Mains

Retrofit Luminaire with

Two Tubes and One Ballast

L

N

HyLite LED Tube

L

N

HyLite LED Tube

AC Mains

Electronic Ballast

Fluorescent Tube

Fluorescent Tube

Electronic Ballast

AC Mains

Retrofit Luminaire with Three or Four Tubes and One Ballast

L

N

L

N

L

N

L

N

AC Mains

Electronic Ballast

AC 

Mains

Fluorescent Tube

Fluorescent Tube

Fluorescent Tube

Fluorescent Tube

Electronic Ballast

HyLite LED Tube

HyLite LED Tube

HyLite LED Tube

HyLite LED Tube

Retrofit Luminaire with Three or Four Tubes and Two Ballasts

L

N

L

N

L

N

L

N

AC Mains

Electronic Ballasts

Fluorescent Tube

Fluorescent Tube

Electronic Ballast

Fluorescent Tube

Fluorescent Tube

AC 

Mains

HyLite LED Tube

HyLite LED Tube

HyLite LED Tube

HyLite LED Tube

Отзывы: