WARNING
!
Single-End Power Connection
Installation/Retrofit Guide
“Single-end” Power Connection Procedure:
1. Ensure Breaker is turned off and no Power is going to the Fixture. 2. Remove Fluorescent Tube and Recycle.
3. Open/Remove Wiring Compartment Cover and Cut-off all Wires connected to the Ballast. Remove the Ballast.
4. Connect the Wires as shown in ( Fig. 1 ) and ( Fig. 2 ).
5. Adapt one-end Wiring method as shown in ( Fig. 3 ) before installing the HyLite LED Tube Light.
a. Live Wire “L” and Neutral Wire “N”, should be separately connected to any one Wire of C1 or C2.
b. The Wire “L” and Wire “N” can be separately connected to more than one Wire from C1 or C2.
c. To avoid the risk of Electric Shock,
DO NOT
connect Wires “L” and “N” together.
d. Use approved Electrical Insulating Tape or Wire Cap to ensure that all the Power Cords which were cut are well Insulated or Capped.
An Energized Wire is a Shock and a Fire Hazard.
6. Close-up the Wiring Compartment.
7. Insert HyLite LED Tube Light in the Lamp Holder.
Note:
Check the Tube to ensure the “Input” end is installed in the Lamp Holder with the line and neutral installed.
8. Once Installation is complete, switch-on Power.
For installing the tube with AC Direct Wire connection, only one end of the tube is designated
as the input side. Ensure only this end is installed in the Powered Lamp Holder. Do not Remove
Cover and/or End Caps. No User-Serviceable Parts inside.
© 2016 ARVA, LLC., USA
www.HyLiteLEDLighting.com
Installation Method for 4 ft. (120cm) Single-end Power Connection
Single-end Power
Wiring Connection
L
N
Input Voltage
AC 100-277V
Luminaire with Magnetic Ballast & Starter
(1) Cut-off all Wires connected to
the Ballast & Starter.
(2) Connect the Wiring of Input & Output
of the Magnetic Ballast.
C1 C2
AC 100-277V
50/60 Hz.
C3 C4
S
HyLite LED Tube Light
(1)
(2)
(2)
Connect
Input Wire
Fig. 1
Luminaire
Fig. 3
L
N
HyLite
LED T
ube Light
Wiring: Connection on one-end only.
Input side is designated on the tube.
HyLite LED Tube Light
L
N
C1
C2
Input Voltage:
AC 100-277V, 50/60 Hz.
HyLite LED Tube Light
C1
Remove Ballast
C2
C3
C4
AC 100-277V
50/60 Hz.
Luminaire with Electronic Ballast
Fig. 2
HyLite LED Tube Light
Retrofit Luminaire with One Tube
L
N
AC Mains
Electronic Ballast
HyLite LED Tube
Electronic Ballast
Fluorescent Tube
AC Mains
Retrofit Luminaire with
Two Tubes and One Ballast
L
N
HyLite LED Tube
L
N
HyLite LED Tube
AC Mains
Electronic Ballast
Fluorescent Tube
Fluorescent Tube
Electronic Ballast
AC Mains
Retrofit Luminaire with Three or Four Tubes and One Ballast
L
N
L
N
L
N
L
N
AC Mains
Electronic Ballast
AC
Mains
Fluorescent Tube
Fluorescent Tube
Fluorescent Tube
Fluorescent Tube
Electronic Ballast
HyLite LED Tube
HyLite LED Tube
HyLite LED Tube
HyLite LED Tube
Retrofit Luminaire with Three or Four Tubes and Two Ballasts
L
N
L
N
L
N
L
N
AC Mains
Electronic Ballasts
Fluorescent Tube
Fluorescent Tube
Electronic Ballast
Fluorescent Tube
Fluorescent Tube
AC
Mains
HyLite LED Tube
HyLite LED Tube
HyLite LED Tube
HyLite LED Tube