SPA
Page 27
5.3.2.1
Control Parameters Submenu (under Startup
Menu)
Summary of Parameters:
Programming sequence to modify the control parameters.
Task: Parameter U6 should be reset from “internal PI-controller” to “1-
step”.
»
press
in Operating Mode,
»
press
or
until “Commissioning Parameters”
appears on the display
»
press
»
press
»
press
»
press
»
press
»
press
or
until the submenu “Operation Mode
Parameters” appears on the display
»
Para-
meter
Description
Possible Settings
Access
Code
U6
Controls
1 Step (On/Off)
MODBUS
Mehrstufig
internal PI-controller
010
P1
Steam generation
output limiter [%]
25-100%
010
E1*
Xp-PI-controller
=100/E1
[Amplification]
[0- 100 %]
010
E2*
Tn-PI-controller
[Integration time]
[0- 255sec.]
010
* Only when internal PI-controller is activated
Sprache/Language
ESC
Commissioning
Parameters
ESC
Commissioning
Parameters
Code 000
ESC
Commissioning
Parameters
Code 000
ESC
Commissioning
Parameters
Code 010
ESC
Commissioning
Parameters
Code 010
ESC
System Test
ESC