hyfire TAURUS TAU-BS-01 Скачать руководство пользователя страница 14

ACOUSTIC SPECIFICATIONS 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* EN 54-3 approved tone. 

 

ACOUSTIC PERFORMANCE 

 

 

 

 

 

 

 

 

 

 

 

 

* EN 54-3 approved tone. 

 

 

 

 

 

 

 

 

 

 

 

 

 

* EN 54-3 approved tone. 

 

VAD SPECIFICATIONS 

 

 

 

 

 

 

Horizontal plane L

AFmax

 @ 1m (dBA)

 

Tone Number 

Angle 

  Average 

15° 

45° 

75° 

105° 

135° 

165° 

Tone 1 * 

81.1 

81.3 

84.6 

85.0 

80.4 

82.7 

82.9 

Tone 2 * 

77.0 

84.3 

77.7 

89.2 

88.3 

86.6 

85.9 

Tone 3 * 

83.2 

84.9 

88.5 

88.7 

89.5 

87.7 

87.6 

Tone 4 * 

82.3 

84.2 

87.0 

87.5 

86.8 

85.2 

85.8 

Vertical plane L

AFmax

 @ 1m (dBA)

 

Tone Number 

Angle 

  Average 

15° 

45° 

75° 

105° 

135° 

165° 

Tone 1 * 

84.0 

89.0 

84.4 

91.6 

87.2 

88.0 

88.2 

Tone 2 * 

87.2 

86.8 

76.7 

96.9 

90.0 

89.1 

91.1 

Tone 3 * 

86.7 

88.1 

85.4 

95.1 

90.4 

90.5 

90.6 

Tone 4 * 

85.4 

87.0 

84.9 

92.9 

89.0 

88.9 

88.9 

Specification 

Value 

Number of tones 

32 

Tone 1 (warble tone) typical sound output * 

88 dB(A) 

Tone 2 (continuous tone) typical sound output * 

91 dB(A) 

Tone 3 (Dutch slow whoop tone) typical sound output * 

91 dB(A) 

Tone 4 (German DIN tone) typical sound output * 

89 dB(A) 

Acoustic output frequency range 

440 Hz to 2900 Hz 

Table 9 

Table 10 

Table 11 

Table 12 

www.hyfirewireless.com 

Hyfire Wireless Fire Solutions Ltd - Unit B12a, Holly Farm Business Park, Honiley,  

Warwickshire, CV8 1NP - United Kingdom 

 

14 

Specification 

Value 

Notes 

Flash frequency 

0.5 Hz 

 

WHITE flash / HIGH power coverage 

Ceiling mounted, 3 m height, 15 m coverage diameter, 

10.61 m x 10.61 m (112.5 m

2

) square coverage. 

 

Ceiling mounted (EN 54-23 open “O” class), 4.6 m 

height, 15 m coverage diameter, 10.61 m x 10.61 m 

(112.5 m

2

) square coverage 

C3-15 (EN 54-23) 

O4.6-15 (EN 54-23) 

RED flash / HIGH power coverage 

Ceiling mounted, 3 m height, 10 m coverage diameter, 

7.07 m x 7.07 m (50 m

2

) square coverage 

C3-10 (EN 54-23) 

WHITE flash  / LOW power coverage 

Ceiling mounted, 3 m height, 10 m coverage diameter, 

7.07 m x 7.07 m (50 m

2

) square coverage 

C3-10 (EN 54-23) 

RED flash / LOW power coverage 

Ceiling  mounted  (EN  54-23  open  “O”  class),  1.7  m 

height,  6  m  coverage  diameter,  4.24  m  x  4.24  m  (18 

m

2

) square coverage 

O1.7-6 (EN 54-23) 

Содержание TAURUS TAU-BS-01

Страница 1: ...gineering standards Appropriate risk assessment should be carried out initially to determine correct design criteria and updated periodically Use only in Taurus fire detection and alarm systems WARRAN...

Страница 2: ...sly if associated with a suitable cover plate TAU BS 01 TAU BSB 23R 01 and TAU BSB 23W 01 are battery powered and they don t need any system cabling installation Picture 1 Battery A lodgement Battery...

Страница 3: ...ATION 9 Set the output visual signal s power applicable only to TAU BSB 23R 01 and TAU BSB 23W 01 See SOUNDER OUTPUT S CONFIGURATION 10 Drill out the required fixing holes on the wall installation pla...

Страница 4: ...quality BATTERY COVER Detach the battery cover by pulling up the tab highlighted in the following picture To reinstall the battery cover insert its two hooks into the device s recesses as indicated in...

Страница 5: ...ollowing picture Drill templates on the wall plate are highlighted in the following picture Make sure that the sound diffuser cone printed on the wall plate corresponds to the acoustic alarm signal ou...

Страница 6: ...sure that the batteries are installed properly with their polarities matching the indications on the device POWERING UP RECOVERY Use this procedure when you fail to link successfully a TAU BS 01 TAU B...

Страница 7: ...REX or from TAU TRM 01 TAU CEM 01 for linking success Consult their user manual LINKING ONE BY ONE One by one linking consists in associating one child device at a time to the Taurus system This opera...

Страница 8: ...ect the required output volume switches combinations and the corresponding volume levels are found on table 3 4 Select the visual emission s power switch settings and the corresponding power levels ar...

Страница 9: ...interrupted tone fast 2800Hz for 150ms then OFF for 150ms 11001 15 HF Continuous 2800Hz continuous 01001 16 Interrupted tone 800Hz for 500ms then OFF for 500ms 01111 17 Interrupted tone medium 1000Hz...

Страница 10: ...Hz continuous 11011 14 800Hz continuous 11001 15 2800Hz continuous 01001 16 800Hz continuous 01111 17 800Hz continuous 01101 18 970Hz for 500ms then OFF for 500ms 01110 19 2850Hz for 500ms then OFF fo...

Страница 11: ...tallation manual For placing the detector plastic cover refer to the following picture Picture 7 Make sure the detector s OWN battery cover is installed to avoid tamper detection events If a detector...

Страница 12: ...ondition call point activation approved detector aerosol heat testers 2 Check the acoustic alarm output of the base sounder 3 Check the visual alarm output of the base sounder TAU BSB 23R 01 TAU BSB 2...

Страница 13: ...01 TAU CEM 01 or TAU EXM 01 network devices 200 m in open space Wireless frequency band 868 MHz Number of wireless channels 66 Radiated power 14 dBm 25 mW Operating temperature range 10 C to 55 C Max...

Страница 14: ...e 4 German DIN tone typical sound output 89 dB A Acoustic output frequency range 440 Hz to 2900 Hz Table 9 Table 10 Table 11 Table 12 www hyfirewireless com Hyfire Wireless Fire Solutions Ltd Unit B12...

Отзывы: