background image

ALTERNATE TONE SET

 

[email protected]

 

L20

-

CWSXX

-

1400 (vA.6)

 

 

Tone 

 

number

 

Tone description

 

DIP switch configuration: 

1, 2, 3, 4 and 5

 

1

 

800Hz continuous

 

11101

 

2

 

1000Hz continuous tone

 

01011

 

3

 

500

-

1200Hz for 3500ms, then off for 500ms

 

10101

 

4

 

800Hz continuous

 

00111

 

5

 

2400Hz continuous

 

10010

 

6

 

800Hz continuous

 

11110

 

7

 

500Hz continuous

 

11100

 

8

 

500Hz continuous

 

10100

 

9

 

2400Hz continuous

 

10001

 

10

 

500

-

1200Hz sweep for 3750ms, then OFF for 250ms

 

10110

 

11

 

990Hz continuous

 

00001

 

12

 

800Hz continuous

 

00101

 

13

 

2800Hz continuous

 

11011

 

14

 

800Hz continuous

 

11001

 

15

 

2800Hz continuous

 

01001

 

16

 

800Hz continuous

 

01111

 

17

 

800Hz continuous

 

01101

 

18

 

970Hz for 500ms, then OFF for 500ms

 

01110

 

19

 

2850Hz for 500ms, then OFF for 500ms

 

01100

 

20

 

800Hz continuous

 

11010

 

21

 

800Hz continuous

 

01010

 

22

 

800Hz continuous

 

11000

 

23

 

970Hz continuous

 

11111

 

24

 

800Hz continuous

 

00000

 

25

 

800Hz continuous

 

00010

 

26

 

660Hz continuous

 

00100

 

27

 

660Hz for 150ms, then OFF for 150ms

 

00110

 

28

 

800Hz continuous

 

10111

 

29

 

800Hz continuous

 

10011

 

30

 

800Hz continuous

 

01000

 

31

 

2900Hz continuous

 

00011

 

32

 

800Hz continuous

 

10000

 

Table 4

 

Содержание HFC-WSR-03

Страница 1: ...to detach the upper sounder body from the base 1 Insert the pins of the compatible key into the holes of one of the two side locking mechanisms 2 Turn the key 90 to the left whilst applying light pres...

Страница 2: ...ted in picture 6 CABLE ENTRIES The sounder base is provided with a knockout entry for the system cables located in the centre of the base picture 7 The side wall of the base has prepared drilling poin...

Страница 3: ...r one can be used Connect to the negative terminals of the control panel s sounder circuit Wiring to these terminal blocks acti vates the main tone set 4 5 Alt Terminal blocks for the line s negative...

Страница 4: ...he DIP configuration column to select the five switch selection settings OUTPUT VOLUME SETTING Use the DIP switch at the back of the sounder body to select the output volume in particular switches 6 a...

Страница 5: ...OFF for 1s 11011 HF Back up interrupted tone 14 2800Hz for 150ms then OFF for 150ms 11001 HF Back up interrupted tone fast 15 2800Hz continuous 01001 HF Continuous 16 800Hz for 500ms then OFF for 500...

Страница 6: ...110 11 990Hz continuous 00001 12 800Hz continuous 00101 13 2800Hz continuous 11011 14 800Hz continuous 11001 15 2800Hz continuous 01001 16 800Hz continuous 01111 17 800Hz continuous 01101 18 970Hz for...

Страница 7: ...firewireless com TECHNICAL SPECIFICATIONS Power supply voltage range 15 40 Vdc 24 Vdc standard value Activated current range volume set to HIGH Dependent upon tone selected 5 8 mA at 24 Vdc Audible fr...

Страница 8: ...to and follow national codes of practice and other internationally recognized fire engineering standards Appropriate risk assessment should be carried out initially to determine correct design criteri...

Отзывы: