WIRING CONNECTIONS
HeatNet Control V3 2.x
Page 52
Figure 32
Heating Method 5: MODBUS (Optional BACnet or LonWorks bridge
— Protocessor)
3 wire Shielded
Modbus
Modbus Termination.
Enable:
Switches DOWN Position.
Disable:
Switches UP position.
Switch shown disabled.
Protocessor Bridge Module Plug-in.
LonWorks or BACnet bridge which
Can be used instead of the
MODBUS input.
Shielded/Twisted Pair Connection
(MSTP/LonWorks)
RJ45 Configuration
and IP connection
NOTE:
Do not plug the Protocessor
module in with power on or the
Protocessor module may be damaged.
The pin headers are located on the control (‘U’ shaped) that the
Protocessor bridge module plugs in directly. Align the sockets on the
Protocessor with the pin headers on the control, then press into place.
Communication from the Protocessor bridge to the H-Net control is also
handled through the sockets.
Next, connect the BACnet or LonWorks network cable to the Protocessor
module or configure the bridge using the software tools. Once connected
use the DIP switch to enable termination.
RJ45 Cat 5
Modbus
Additional Bulletins and Instructions for Configuring BACnet or LonWorks are available on the website.
DIP Switch shown:
NOT
Terminated
The (2) LEDs on the RJ45 indicate:
GREEN: Transmit Data
YELLOW: Received Data