3.3

Connections

The Thermo-Tuff is supplied with a 4 metre unterminated cable. The wire colours are:

When installing the Thermo-Tuff a drip loop should be used to protect the cable gland from any water ingress.

The Thermo-Tuff cable screen must be connected to a good system earth point.

3.4

Output Circuit Design

The output circuit should be designed such that V

A

 is 

between 10v and 28v DC. This can be checked by 
calculating the following:

V

A

 = V

PSU

 - (I*R)

Where I is 4mA for the maximum V

A

 and 20mA for the 

minimum V

A

. R is the total resistance of the circuit 

including the cable.

4

Troubleshooting

Inaccurate Temperature

Check the PLC input scaling
Check the voltage across the TT01.

Noisy Signal

Check total resistance in the loop.

No Current

Check polarity

Output clamps at less than 20mA

Check the resistance of the cable and the control system input.
Check the voltage across TT01

5

Declaration of conformity

Wire Colour

Description

Red

Current Loop Positive

Blue

Current Loop Negative

Screen

Earth

This device complies with part 18 of the FCC Rules.

This device is designed and manufactured in 
accordance with the following directives:

Local regulations regarding the 
disposal or recycling of waste 
electronic equipment must be 
followed.

2004/108/EC

The Electromagnetic Compatibility 
Directive and its amending directives

Power

Supply

Thermo-Tuff

Control System

Input

+

-

+

-

+

-

V

PSU

V

A

 

SUNSTAR传感与控制 http://www.sensor-ic.com/ TEL:0755-83376549 FAX:0755-83376182 E-MAIL:[email protected]

SUNSTAR自动化 http://www.sensor-ic.com/ TEL: 0755-83376489 FAX:0755-83376182 E-MAIL:[email protected]

Содержание HD0476

Страница 1: ...on 1 0 1 Revision Date January 2011 Thermo Tuff User Guide SUNSTAR传感与控制 http www sensor ic com TEL 0755 83376549 FAX 0755 83376182 E MAIL szss20 163 com SUNSTAR自动化 http www sensor ic com TEL 0755 83376489 FAX 0755 83376182 E MAIL szss20 163 com ...

Страница 2: ...ement Range 0 80 C Storage Temperature 10 80 C Voltage Range 10 28v DC Reverse Polarity Protected IP Rating IP68 Weight 600g including 4m cable Installed T90 56s 2 Mechanical Installation 2 1 Dimensions 2 2 Installation Options The sensor can be mounted vertically or horizontally The sensing surface must touch the material being measured The Thermo Tuff is designed to be maintenance free and does ...

Страница 3: ...n Mounting Sleeve so that it is flush with the end of the sleeve It is retained with two grub screws The Sleeve is then fitted in the Mounting Collar and the retaining bolts used to secure the assembly 3 Electrical Installation 3 1 Power The Thermo Tuff is designed to be powered by the 4 20mA current loop It does not have connections for an external power supply 3 2 Analogue Output The Thermo Tuff...

Страница 4: ...put scaling Check the voltage across the TT01 Noisy Signal Check total resistance in the loop No Current Check polarity Output clamps at less than 20mA Check the resistance of the cable and the control system input Check the voltage across TT01 5 Declaration of conformity Wire Colour Description Red Current Loop Positive Blue Current Loop Negative Screen Earth This device complies with part 18 of ...

Отзывы: