background image

6

Pump 
Operation

As  the  motors  are  oil  filled,  no 
lu bri ca tion  or  other  main te nance
is required. 
If  a  seal  failure  unit  is  used,  no 
at ten tion  is  necessary  as  long  as
the  seal  shows  sat is fac to ry 
operation.
If  seal  failure  is  not  used,  the
pump should be lifted once every 
two  years  and  the  oil  be  drained
from  the  seal  cham ber  to  check
for water.
If the pump is used on a Hydr-O-
Rail  system,  it  should  be  lifted
once  every  six  months  and
checked for cor ro sion and wear.
Generally  these  pumps  give  very
re li able  service  and  can  be 
expected  to  operate  for  years 
on  normal  sewage  pump ing 
without failure.

Lightning:
In some areas where con sid er able
light ning 

occurs, 

it 

is 

recommended  that  a  light ning
arrestor  be  installed  at  the 
control panel.
Complete  data  on  lightning
arrestors  and  cost  is  avail able
from  the  factory.  Lightning 
ar res tors  are  good  in sur ance
against 

damage 

to 

an 

ex pen sive motor.

Starting Systems:
1.  Turn  H-O-A  switch  to  Off

position,  then  turn  on  main 
circuit breakers.

2.  Open  all  discharge  valves 

and  al low  water  to  rise  in 
sump pump.

3.  Turn  H-O-A  switch  to  Hand

po si tion  on  one  pump  and
notice  op er a tion.  If  pump  is
noisy  and  vi brates,  rotation  is
wrong.  To  change  rotation
interchange any two line leads
to  motor.  Do  not  in ter change
main in com ing lines. 
If duplex
sys tem, check second pump in
the same manner. 

4.  Now set both H-O-A switches

to  Auto  position  and  allow
water  to  rise  in  sump  until
one  pump  starts. Allow  pump
to  operate  until  level  drops  to
turn-off point.

5.  Allow  sump  level  to  rise  to

start  other  pump.  Notice  run
lights  on  panel;  pumps  should
alternate  on  each  suc ces sive
cycle of op er a tion. 

6.  Turn  both  H-O-A  switch es  to

Auto position and allow sump
to  fill  to  the  over ride  control
level.

7.  Turn  both  switches  to  Auto 

po si tion  and  both  pumps
should  start  and  operate 
to geth er  until  level  drops  to
turn-off point.

8.  Repeat  this  operation  cycle

sev er al  times  before  leav ing
the job.

9.  Check  voltage  when  pumps 

are  operating  and  check  the
amp  draw  of  each  pump.
Check  amps  on  each  wire  as 
sometimes  a  high  leg  will
exist.  One  leg  can  be 

some what  higher  (5  to  10%)
without  caus ing  trouble.  For
excessive  amp  draw  on  one
leg, the power company should
be consulted.

Pump
Maintenance

Servicing Instructions:

IMPORTANT: 

Read 

all 

in struc tions  before  replacing
any parts.

WARNING:  Before  han dling
these  pumps  and  controls,
always  dis con nect  the  power
first.
Do  not  smoke  or  use  sparkable
elec   trical devices or flames in a
sep tic  (gaseous)  or  possible 
septic sump.

Field Service on Motor:
All  submersible  motors  can  be
ser viced  (out  of  warranty)  in  the
field by any reliable motor service
shop.  Any  pump  (in  warranty)
must  be  re turned  to  the  factory 
for  service  or  re paired  in  an 
au tho rized  Hydromatic  service
center.  Charg es  will  not  be
allowed  if  (in  warranty)  pump 
is  taken  to  a  motor  repair 
shop  that  is  not  an  authorized
Hydromatic service center.
When  field  service  is  per formed
on  a  pump,  these  in struc tions
should be carefully followed.

Replacing Stator:
If  motor  winding  is  burned  or
short ened,  it  can  be  rewound  or
replaced with new factory wound
stator.  Refer  to  sec tion al  drawing
of  pump  and  mo tor  and  use  the
following  steps  to  re move  and
replace stator.
1. If  stator  only  is  dam aged, 

it  may  not  be  necessary  to
completely dismantle pump as
stator and hous ing can be lifted
from  pump  without  dis turb ing
seals or bear ings.

2. Drain  all  oil  from  upper 

housing,  remove  from  upper
housing, re move drain plug in

Содержание S

Страница 1: ...25 304 1 2010 Pentair Pump Group Inc Installation and Service Manual NOTE To the installer Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system For use with product built with Regal Beloit Marathon motor ...

Страница 2: ...erate without damage but the seal should be checked immediately after failure is indicated NOTE Failure to install such a device negates all warranties by Hydromatic Pump The S submersible pump is supplied for 1 and 3 phase and for 200 230 460 or 575 volts Pump is supplied with 30 feet of power cord and or 30 feet of auxiliary control cord Longer cable lengths can be furnished but must be specifie...

Страница 3: ...controls one set at turn off one set at turn on for one pump one set at turn on for two pumps and one set at turn on for three pumps Pumps alternate each successive cycle Three pumps operate together only if sump level rises to the fourth control second override This control also brings on the third pump in case of failure of either or both of the first two pumps Alarm Controls The alarm level is ...

Страница 4: ... between sump and panel a Walkie Talkie radio is useful Installing 3900 Mercury Switch Controls The controls are supported by a mounting bracket that is attached to sump wall or cover or to the NEMA 4 junction box Cord snubbers are used to hold the cord in place Control lever can be changed at any time by loosening the snubber and readjusting cord length In either simplex or duplex system the lowe...

Страница 5: ...ed for use in making the installation All wires should be checked for grounds with an ohmmeter or Megger after the connections are made This is important as one grounded wire can cause considerable trouble Figure 1 CONNECTION DIAGRAM FOR LEADS IN MOTOR AND CONNECTION BOX Y WYE MOTOR CONNECTIONS 230 VOLTS 460 VOLTS GREEN GREEN L3 L2 L1 L3 L2 L1 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 HEAT SENSORS AND S...

Страница 6: ...f operation 6 Turn both H O A switches to Auto position and allow sump to fill to the override control level 7 Turn both switches to Auto position and both pumps should start and operate together until level drops to turn off point 8 Repeat this operation cycle several times before leaving the job 9 Check voltage when pumps are operating and check the amp draw of each pump Check amps on each wire ...

Страница 7: ...8 Drain oil from chamber If oil is clean and no water is present seals can be considered satisfactory to reuse 9 Check top bearing If clean and does not turn rough bearings can be reused and it is not necessary to completely dismantle pump to change bearings If bearings are damaged with dirt or heat they must be replaced See additional instructions on replacing seals and bearings Remember to reins...

Страница 8: ...e This will force out lower seal if not already removed 9 Remove snap ring that holds upper seal Pull seal if it is free If not free it can be forced off when shaft is removed 10 Remove 4 bolts that hold bearing housing in place Set assembly in upright position and bump end of shaft on hardwood block This will push the bearing from the housing and will force upper seal from shaft 11 Use bearing pu...

Страница 9: ...p in the closed position Check in sump to be sure control is free 3 Selector switch may be in the Hand position Pump does not deliver proper capacity 1 Discharge gate valve may be partially closed or partially clogged 2 Check valve may be partially clogged Raise level up and down to clear 3 Pump may be running in wrong direction Low speed pumps can operate in reverse direction without much noise o...

Страница 10: ...P 200 3 60 1 1150 RPM For pumps manufactured after 11 12 73 24407C225 Stator 1 2 HP 1 HP 230 460 3 60 1 1150 RPM 24407C226 Stator 1 2 HP 1 HP 575 3 60 1 1150 RPM 14694 203 1 Stator 3 4 HP 1 HP 200 1 60 1 1750 RPM 14694 003 1 Stator 3 4 HP 1 HP 230 1 60 1 1750 RPM 24407C212 Stator 3 4 HP 1 HP 200 3 60 1 1750 RPM 24407C213 Stator 3 4 HP 1 HP 230 460 3 60 1 1750 RPM 14695 603 1 Stator 3 4 HP 1 HP 575...

Страница 11: ...11 2 3 4 6 7 8 9 11 12 14 15 16 17 18 19 20 21 22 23 24 25 48 26 27 28 29 33 32 31 30 46 45 44 41 43 42 40 38 37 36 34 35 47 30 49 10 1 S ...

Страница 12: ...__________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ _____________...

Страница 13: ...__________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ _____________...

Страница 14: ...rdance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units which are not installed in accordance with applicable local codes ordinances and good trade practices e if the unit is moved from its original installation location f if unit is used for purposes other tha...

Страница 15: ......

Страница 16: ...g Line Voltage _________________________________Actual ___________________________________ Voltage to Pumps _____________________________________Actual ___________________________________ Type of Junction Box __________________________________Manufacturer of Junction Box ______________ Are Floats Installed in Wet Well Yes No Are Floats Set to Engineer s Specs Yes No Are Floats Wired for Proper Seq...

Отзывы: