General 

Information

Attention: 

This manual contains important 

information for the safe use of 

this product. Read this manual 

completely before using this product 

and refer to it often for continued 

safe product use. Reasonable 

care and safe methods should be 

practiced. Check local codes and 

requirements before installation.
Unpacking Pump:
Remove pump from carton. When 

unpacking unit, check for concealed 

damage. Claims for damage must be 

made at the receiving end through 

the delivery carrier. Damage cannot 

be processed from the factory.
WARNING: Before handling 

these pumps and controls, always 

disconnect the power first. Do not 

smoke or use sparkable electrical 

devices or flames in a septic 

(gaseous) or possible septic sump.
California Proposition 65 Warning:

 This product and 

related accessories contain chemicals 

known to the State of California to 

cause cancer, birth defects or other 

reproductive harm.
Application:
These pumps are designed for 

on-site residential sewage discharge 

applications with a pH ranging from 

6 to 9, specific gravities from 0.9 to 

1.1, viscosities ranging from 28 to 35 

S.S.U., and temperatures up to 140 

degrees Fahrenheit. 

Pumps Not Operating or 

in Storage:
Pumps with carbon ceramic seals 

must have impellers manually 

rotated (6 revolutions) after sitting 

nonoperational for 3 months or 

longer and prior to electrical start-up.
Seal Failure Probes:
All hazardous location submersible 

pumps have two factory-installed 

moisture detectors (seal failure 

probes). They are in a normally open 

series circuit, in the seal chamber. 

Under normal operating conditions, 

the circuit remains open. If the 

lower seal leaks and moisture enters 

this chamber, the moisture would 

settle to the bottom of the chamber 

and will complete the circuit 

between the moisture detectors. 
This circuit must be connected to a 

sensing unit and signaling device. 

This is supplied in a Hydromatic

®

 

control panel. 
NOTE: Failure to install such a 

device negates all warranties by 

Hydromatic pumps. 
Heat Sensors:
All motors in this family have heat 

sensors on or embedded in the 

motor winding to detect excessive 

heat. This prevents damage to the 

motor. If the sensor trips due to 

excessive winding temperature, the 

starter in the panel breaks power to 

the pump. Once the sensor resets, 

the starter is to be reset (automatic 

for F.M.) for continued operation 

of the pump. This circuitry is 

supplied in a Hydromatic control 

panel. The sensors are set to trip at 

120° Celsius. 
NOTE: Failure to install such 

circuitry would negate F.M. 

approval and all warranties by 

Hydromatic pumps. 
Power Cords:
The power cord and heat sensor 

seal failure cord are potted into the 

connection box cap. The cords must 

not be spliced. 
NOTE: Each cable has a green 

lead. This is the ground wire 

and must be grounded properly 

per NEC, and/or local codes. 

During normal maintenance 

procedures, power cords should be 

inspected for abnormal wear and 

replaced accordingly.
Overload Heaters:
If the Hydromatic electrical panel 

is not used, starters with 3-leg 

overload relay must be supplied 

on three-phase pumps. Each leg is 

to have an identical heater sized 

in accordance with the nameplate 

amps on the motor housing. The 

amp draw on these submersible 

motors is slightly higher than a 

corresponding horsepower surface 

motor, so heaters must be sized by 

the nameplate rating. 
Single-phase pumps with capacitor 

start have a run and a start winding, 

each drawing a different current. To 

adequately protect these windings 

with the appropriate heaters, consult 

the factory. 
NOTE: Red lead is always 

start winding of pump using  

single-phase.

Pump Installation 

Installing Pump in Sump:

Before installing pump in sump, 

lay it on its side and rotate impeller. 

Impeller may be slightly stuck due 

to factory test water so it must be 

broken loose with a small bar or 

screwdriver in edge of vanes. The 

impeller should turn freely. Do 

not connect the power until after 

this test. 
Clean all trash and sticks from 

sump and connect pump to piping. 

A check valve must be installed on 

each pump. 
Location:
If pumps are installed in an 

existing basin or concrete sump, 

the piping can either be connected 

permanently or rails and brackets 

can be furnished for mounting to 

walls of basin. In either case, be 

sure the Hyromatic solids handling 

ball check valve is used and that the 

pumps are submerged in a vertical 

position. The complete factory-built 

packaged system is recommended 

for the most satisfactory installation 

and generally for the lowest cost 

where expensive installation labor 

is involved. 
Making Electrical Connections:

All electrical wiring must be in 

accordance with local code, and 

Содержание HPGFHX

Страница 1: ...sible party who maintains the system MODELS HPGFX HPGHX HPGFHX HPGHHX Class I Division 1 Groups C D FM HAZARDOUS LOCATION SUBMERSIBLE GRINDER PUMPS INSTALLATION AND SERVICE MANUAL For use with product...

Страница 2: ...r in the panel breaks power to the pump Once the sensor resets the starter is to be reset automatic for F M for continued operation of the pump This circuitry is supplied in a Hydromatic control panel...

Страница 3: ...nel schematic If a control panel is supplied by others it must allow heat sensor and seal failure terminations Installing Sump Level Control Float Controls In either simplex duplex or triplex systems...

Страница 4: ...an authorized Hydromatic service shop This will ensure the integrity of the hazardous location rating of the pump and comply with our warranty requirements Disconnecting Pump Cords If a Hydromatic ha...

Страница 5: ...5 Wiring Diagrams...

Страница 6: ...24 005170081 Screw 4 25 009750031 Snap Ring 1 26 109150022 Seal Housing 1 27 009200011 Shaft Seal Upper 1 28 005680071 Cap Screw 4 29 005170051 Screw 4 30 24407C209 Stator 7 1 2 hp 230 460V 3 1 24407...

Страница 7: ...9750031 Snap Ring 1 26 109150022 Seal Housing 1 27 009200011 Shaft Seal Upper 1 28 005680071 Cap Screw 4 29 005170051 Screw 4 30 24407C209 Stator 7 1 2 hp 230 460V 3 1 24407C206 Stator 5 hp 230 460V 3...

Страница 8: ...680071 Cap Screw 4 29 005170071 Screw 4 30 22574C216 Stator 7 1 2 hp 230 460V 3 1 22574C215 Stator 7 1 2 hp 208V 3 1 146920031 Stator 5 hp 230 460V 3 1 22574C201 Stator 5 hp 208V 3 1 22574C204 Stator...

Страница 9: ...1 22574C215 Stator 7 1 2 hp 200V 3 1 146920031 Stator 5 hp 230 460V 3 1 22574C201 Stator 5 hp 200V 3 1 22574C204 Stator 5 hp 575V 3 1 22574C200 Stator 5 hp 230V 1 1 22574C210 Stator 3 hp 230 1 60 1 1...

Страница 10: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 11: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 12: ...lure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services an...

Отзывы: