background image

INTRODUCTION

Thank you for selecting the HRC-100-RS-HW Hydro-Rain

®

 sensor. This sensor 

will provide conservation, convenience, and flexibility to your fully automatic 

watering system. Never again will you see your sprinklers running on a rainy 

day. After a set amount of rain has fallen the sensor engages a switch that  

will prevent the timer from watering. Once the rain sensor has dried  

sufficiently or the temperature rises above 37˚F (3˚C), the sensor allows  

normal sprinkler operation.

INSTALLATION INSTRUCTIONS

Mounting

The HRC-100-RS-HW sensor includes 2 mounting options.

  1. ½" Threaded Adapter

  2. Rain Gutter or flat surface adapter

Mount the sensor where it will be exposed to direct, unobstructed rainfall  

(but away from sprinkler spray). The switch-housing portion must be upright 

(see Figure 1).

Hints for mounting:

A. Mount as close as possible to the timer. This will cause the wire run to be 

shorter, which minimizes the possibility of wire breaks.

B. Mount in the highest possible position where rain can fall directly upon the 

sensor.

C. As described in the “Operation” section of this manual, “reset rate” refers to 

the amount of time it takes the sensor to dry out sufficiently for the sprinkler 

system to be allowed to come back on. The mounting location will affect this 

rate and should be taken into consideration should extreme conditions exist. 

For example, mounting the sensor on a very sunny, southeastern end of 

a building may cause the sensor to dry out sooner than desired. Similarly, 

mounting on the northern end of a building with constant shade may keep the 

sensor from drying soon enough. Some experimentation and use of the “vent 

ring” (as described later) will usually yield satisfactory results. 

Once the sensor is mounted, run the wire to the controller, using wire clips 

every few feet to fasten it. If an extension to the wire provided is needed, use the 

following table to determine the minimum wire gauge needed:

Wiring

Important: The sensor is sold and designed for 24-Volt irrigation controllers 

only. All wiring must conform to applicable local codes.

The two most common wiring situations are detailed below. For non-standard 

wiring situations, please consult your distributor.

A. 24-Volt Solenoid Valves Only (No booster pump) (See Figure 2) With the two 

wires from the sensor at the controller, locate the “common ground” wire  

of the solenoid valves. If it is connected to the common terminal on the  

controller disconnect it. Attach one wire of the sensor to the “common”  

terminal (usually marked “COM”) on the controller. Attach the other wire of 

the sensor to the common wire leading to the valves. Note: The common wire 

to the valves does not have to be interrupted at the controller. The sensor 

may be wired anywhere along the common wire line.

B. 24-Volt Solenoid Valves with booster pump (See Figure 3). Locate the  

common wire to the solenoid valves and the common wire lead to the coil  

of the relay that starts the pump. If these two wires are connected to the 

“common” terminal on the controller, disconnect both of them. Twist these 

two wires together along with one wire from the sensor and secure with a 

wire nut. Attach the other wire of the sensor to the “common” terminal on the 

controller. 

Note: The pump circuit output must be 24 volts in this situation if 

different do not proceed.

  25-50 ft. 

50-100 ft. 

100 ft. or more

 

20 AWG 

18 AWG 

16 AWG

Extension needed: 

then use:

Отзывы: