background image

II. 

ELECTRONICALLY ACTUATED PRESSURE REDUCING VALVE

 1. 

INTRODUCTION

 

 

The PRV-71H (electronically operated) is an electronically actuated, spring loaded diaphragm type gas pres-
sure reducing and shut-off valve.  Its purpose is to reduce and control downstream pressure between 15 to 45 
psig.  The outlet pressure is manually adjusted by the position of the lock nuts.  The electronic actuator is spring 
loaded normally closed and upon loss or disconnection of power, then the spring will move the pressure reduc-
ing valve to the closed position.  Upon recieving or restoring power, the electronic actuator will close an inter-
nal solenoid valve and start an internal motor driven pump that is used to force the ram down until it reaches the 
manually set operating position.  

 2. 

INSTALLATION

 

 

Because of its weight the PRV-71H (electronically operated) should always be supported.  An optional wall-
mounting bracket is available for fast and easy installation.  This wall mounting bracket includes four 

3

8

"x 1" 

mounting slots.  The PRV should be installed in the upright position.

 

 

Inlet and outlet connections to the pressure reducing valve are 

3

4

" or 1" FNPT depending on the model chosen.  

A label is provided to indicate the direction of fl ow and help identify the inlet and the outlet.  There is also a 

1

4

" FNPT vent connection above the outlet connection in case of diaphragm failure and it is recommended that 

1

2

" schedule 80 carbon steel vent piping be used.  Vent piping should also slope downward at least 2 degrees to 

prevent water/moisture entry and an insect screen must be installed on the vent pipeline outlet to prevent insects 
from blocking the pipeline.

 

 

The installation of this valve should be downstream of any chlorine fi lters and drip legs, and a pressure gauge 
should be mounted on the downstream side of the valve to monitor outlet pressure.

 

 

Depending on the model, the electronic actuator will require either a 120 or 240 VAC (50/60 Hz) single phase 
power supply connected to the line terminals on the actuator unit with the ground line connected to the screw 
underneath the common (COM).  The unit also includes a contact relay offering both normally open (N.O.) and 
normally closed (N.C.) connections, and their proper wiring location can be seen on the valve.  To get remote 
closure of the actuator based on an alarm condition, wire a SPST switch into the L1 (phase) side of the power 
line.  When operating, the valve operator requires 170 VA.

 3. 

OPERATION

 

 

With voltage applied to the electronic actuator, an internal solenoid valve will close and a motor driven pump 
will apply pressure to a spring loaded piston.  The ram valve which is connected to this piston will move down 
into position set by the lock nuts.  Once the lock nuts hit the bottom of the yoke, the resistance will be picked 
up by the actuator and the motor will stop, holding the ram valve in place.  Thus, the downstream pressure is set 
by the position of the lock nuts.  Lowering the lock nuts will reduce the amount of tension applied to the load-
ing spring, lowering downstream pressure, while raising the lock nuts will increase the tension applied to the 
loading spring, increasing the downstream pressure.

 

 

Warning:

  Do not adjust the lock nuts while the actuator is on.  Doing so will result in damage of the actuator.  

To adjust the outlet pressure remove from power source and adjust, then re-apply power to get new pressure set-
ting.  Repeat until the correct outlet pressure is achieved

 

 

When in position, the ram valve compresses an internal spring, which in turn presses down on a diaphragm and 
opens up the orifi ce between the valve seat and valve plug.  This opening allows for gas to enter through the 
reducing valve at a controlled pressure.  Downstream pressure is regulated by the counteracting forces on the 
diaphragm between the spring and the gas. For example, when fl ow demand is increased there will be less force 
acting up on the diaphragm.  This will allow the spring to expand down more, enlarging the orifi ce and allowing 
more gas fl ow into the regulator in order to establish a new diaphragm equilibrium position.

 

 

When power is lost, the solenoid valve will open and the ram valve will go up out of contact with the loading 
spring.  This removes tension on the loading spring, causing the diaphragm to move up and the pressure reduc-
ing valve to close.

4

Содержание PRV-71H Series

Страница 1: ...e carefully designed and tested for years of safe accurate field service All Hydro Instruments systems are tested prior to shipment All Hydro Instruments products are made of the finest materials To ensure best operation read these instructions carefully and completely and store them where all maintenance personnel will have access to them 1 ...

Страница 2: ...Maximum Pressure 600 PSI 41 Bar Outlet Pressure Range 0 45 PSI 0 3 Bar See Section I 4 for manual PRVs Section II 4 for Actuated PRVs for more information Operating Temperature 15 F 26 C to 225 F 107 C Operating Temperature 15 F 26 C to 150 F 65 C Inlet Outlet Connections FPT or 1 FPT Vent Connection FPT See Section I 2 for manual PRVs Section II 2 for Actuated PRVs for more information on install...

Страница 3: ...e installed on the outlet of the vent piping to prevent insects from blocking the pipeline The valve should be installed downstream of the chlorine filter and liquid traps drip legs A pressure gauge should always be installed in the downstream piping to indicate the reduced pressure 3 OPERATION The outlet pressure is adjustable by means of the Adjustment Screw PRH 396G 8000 By rotating the Upper E...

Страница 4: ...crew underneath the common COM The unit also includes a contact relay offering both normally open N O and normally closed N C connections and their proper wiring location can be seen on the valve To get remote closure of the actuator based on an alarm condition wire a SPST switch into the L1 phase side of the power line When operating the valve operator requires 170 VA 3 OPERATION With voltage app...

Страница 5: ...with the actuator contact Hydro Instruments or your local Hydro Instruments sales representative If the actuator no longer is able to open the valve then it may require replacement Parts Maintenance Kits are offered and contain the parts necessary to accomplish the recommended mainte nance as well as a parts diagram Note Please refer to the parts diagram for those items included in the Part Mainte...

Страница 6: ... 26 A B C 27 A B C 29 A B 19 B 20 3 4 11 2 1 8 9 10 17 18 5 6 7 16 25 28 30 31 23 22 21 A B C 11 12 14 15 13 15 12 14 13 15 Date 2018 01 05 v1 EXPLODED VIEW Dwg No PRV 71H EXP PRESSURE REDUCING AND SHUTOFF VALVE 6 ...

Страница 7: ... bolt 1 19A Lower Valve Body 3 4 1 PRH 23077 8000 19B Lower Valve Body 1 1 PRH 23077 12000 20 Hex Nut 3 8 16 6 BTH STA 145M 21A Trim Capsule Assembly 8000 PPD 1 PRH 668 8000 21B Trim Capsule Assembly 12 000 PPD 1 PRH 668 12000 21C Trim Capsule Assembly 16 000 PPD 1 PRH 668 16000 22 PM Gasket 1 GAH 334C 8000 23 PM Valve Screen 1 PRH 433S 8000 24A Valve Body Capsule 8000 PPD 1 PRH 433A 8000 24B Valv...

Страница 8: ... 23 11 13 22 10 1 2 3 4 5 6 7 8 9 28 29 30 A B 31 32 A B C 33 A B C 34 35 36 37 27 A B C 20 21 21 18 19 12 24 19 18 20 21 Date 2019 09 27 v1 EXPLODED VIEW Dwg No PRV 71H ELE EXP ELECTRONIC PRESSURE REDUCING AND SHUTOFF VALVE 8 ...

Страница 9: ...PRH 639A 8000 23 Diaphragm Bolt pre assembled press fit with base 1 24 Diaphragm Bolt Base with o ring groove pre assembled with bolt 1 25A Lower Valve Body 3 4 1 PRH 23077 8000 25B Lower Valve Body 1 1 PRH 23077 12000 26 Hex Nut 3 8 16 6 BTH STA 145M 27A Trim Capsule Assembly 8000 PPD 1 PRH 668 8000 27B Trim Capsule Assembly 12 000 PPD 1 PRH 668 12000 27C Trim Capsule Assembly 16 000 PPD 1 PRH 668...

Страница 10: ... C 27 A B C 29 A B 19 B 20 3 4 11 2 1 8 9 10 17 18 5 6 7 16 25 28 30 31 23 22 21 A B C 11 12 14 15 13 15 12 14 13 15 Date 2018 01 15 v1 EXPLODED VIEW Dwg No PRV 71H NH3 EXP PRESSURE REDUCING AND SHUTOFF VALVE AMMONIA 10 ...

Страница 11: ...Hex Nut 3 8 16 Stainless 6 BTH STA 145M SS 21 A Trim Capsule Assembly 4000 PPD Ammonia 1 PRH 668 8000 SS 21 B Trim Capsule Assembly 6000 PPD Ammonia 1 PRH 668 12000 SS 21 C Trim Capsule Assembly 8000 PPD Ammonia 1 PRH 668 16000 SS 22 PM Gasket 1 GAH 334C 8000 23 PM Valve Screen Hastelloy 1 PRH 433S 8000 HC 24 A Valve Body Capsule 316SS 4000 PPD Ammonia 1 PRH 433A 8000 SS 24 B Valve Body Capsule 31...

Страница 12: ...13 22 10 1 2 3 4 5 6 7 8 9 28 29 30 A B 31 32 A B C 33 A B C 34 35 36 37 27 A B C 20 21 21 18 19 12 24 19 18 20 21 Date 2019 09 27 v1 EXPLODED VIEW Dwg No PRV 71H ELE NH3 EXP ELECTRONIC PRESSURE REDUCING AND SHUTOFF VALVE AMMONIA 12 ...

Страница 13: ...th o ring groove pre assembled with bolt 1 25 A Lower Valve Body 3 4 1 PRH 23077 8000 25 B Lower Valve Body 1 1 PRH 23077 12000 26 Hex Nut 3 8 16 Stainless 6 BTH STA 145M SS 27 A Trim Capsule Assembly 4000 PPD Ammonia 1 PRH 668 8000 SS 27 B Trim Capsule Assembly 6000 PPD Ammonia 1 PRH 668 12000 SS 27 C Trim Capsule Assembly 8000 PPD Ammonia 1 PRH 668 16000 SS 28 PM Gasket 1 GAH 334C 8000 29 PM Val...

Страница 14: ...1 2 64 7 7 8 199 1 2 13 2 13 16 71 2 13 16 71 1 25 4 PLACES 3 8 10 4 PLACES 2 3 4 69 3 4 or 1 FNPT Outlet 1 4 FNPT Vent connection 3 4 or 1 FNPT Outlet 1 4 FNPT Vent connection Date October 2015 DIMENSIONAL DRAWING Dwg No PRV 71H DIM PRESSURE REDUCING AND SHUTOFF VALVE 14 ...

Страница 15: ... 2 1 2 64 1 4 FNPT Vent connection 2 13 16 71 1 2 13 7 7 8 199 2 13 16 71 3 8 10 4 PLACES 1 25 4 PLACES 2 3 4 69 3 4 or 1 FNPT Outlet 3 4 or 1 FNPT Outlet 1 4 FNPT Vent connection Date 2019 09 16 v1 DIMENSIONAL DRAWING Dwg No PRV 71H ELE DIM ELECTRONIC PRESSURE REDUCING AND SHUTOFF VALVE 15 ...

Страница 16: ...GROUND NEUTRAL LINE LINE NEUTRAL GROUND Common Normally Normally Closed Open GROUND NEUTRAL LINE COM N O N C Date 2019 09 16 v1 Dwg No PRV PCB 1 PRV 71H ELE CIRCUIT BOARD 16 ...

Страница 17: ...THERMOSTAT HEATER POWER CORD THERMOSTAT PRV 71H ELE WITH HEATER GREEN LED INDICATOR FRONT FLAT PATTERN VIEW BACK FLAT PATTERN VIEW HEATER POWER CORD THERMOSTAT HOOK AND LOOP FASTENERS Date 2019 09 16 v1 HEATER for PRV 71H and PRV 71H ELE 17 ...

Отзывы: